1
1.0 INTRODUCTION
Magnacast
II
series speaker systems are designed for indoor or outdoor wet applications. The
Magnacast
II
produces 90 degrees of acoustic energy and excels in high ambient noise
environments. It has an operating temperature range of -20°C to 60°C.
1.2.
Magnacast II
Distributed Audio Speaker
The
Magnacast II
Distributed Audio speaker has five field-selectable power taps that run off of
25V, 70V, and 100VRMS audio systems. The taps can easily be changed by turning a knob.
The speaker has an integrated DC blocking capacitor that allows the fire alarm control panel to
conduct circuit supervision. The speaker was designed to meet UL Standard 1480 (Speakers
for Fire Protective Signaling Systems) and ULC S541 (Speakers for Fire Alarm Systems).
Magnacast II
Distributed Audio Specifications:
Broadband
100V Tap Setting
Speaker Output @ 1 meter (dB)
45W
139
32W
137
24W
136
16W
134
8W
131
70V Tap Setting
Speaker Output @ 1 meter (dB)
24W
136
16W
134
12W
133
8W
131
4W
129
25V Tap Setting
Speaker Output @ 1 meter (dB)
3W
128
2W
126
1.5W
124
1W
122
.5W
119
Power Tap Selections and dB Rating
Содержание Magnacast II