4.2.2
Potential free emergency button (Sensor-2)
The emergency call button can be connected directly to the
EXT
jack or to the
X2
plug on the sub-communication unit.
Requirements for an emergency call button according to EN81-70:
Symbol: Bell sublime.
Centre of the button >90cm (<110cm) from cabin floor.
Surface ≥ 490mm
2
.
Panel orientation is portrait: alarm button must be the first button from the bottom.
Panel orientation is landscape: alarm button must be the first button from the left.
Use only small signal switches or relay contacts. Do not use 230 V contact material, since it may not give a reliable contact.
If the emergency button is not isolated, i.e. older panels with only a single alarm contact for the alarm horn, the accessory
EA-NT-IN (
10.7) can be used to ensure isolation.
PIN
Function
Colour Specification
3
Emerg contact (EC)
black
On
-potential, beware isolation
6
GND
yellow On
-potential, beware isolation
Wiring for normally closed contacts
NC-contact
Caution: In case of horn supply loss: Emerg. call
connect to
X2
of sub-comm.-unit
or
EXT
-jack PIN 3/6
Wiring for normally open contacts:
NO-contact
connect to
X2
of sub-comm.-unit
or
EXT
-jack PIN 3/6
Adjust EasyAlarm® to the type of contact to be used (Normally open / Normally closed). Shipping: normally open,
configuration:
4.2.2.1
Remote controlled emergency button
EA-LMK70C/T: if a remote-controlled button is used
open drill hole INT inside the housing and connect
coil wires to
X7:
Lamp(+) and ECTest(
-
) (max. 300 mA/Open-Collector).
4.2.3
Alarm signal S3 (Sensor-3)
EA-LMK70C/T: Connect signal S3 (10 to 50 V AC or DC) to
X7
: S3 (IN). The polarity and the reference potential may
be arbitrary. Adapt alarm condition
8
Retrofitting of existing plants with
single-contact button for the alarm horn
use EA-NT-IN (
RJ45-cable
2-wire / max. 3 m
Art. No: 118.0140
NO/EC
C/EC
EA-NT-IN
NC
NO
-
C
+
-
NC/EC
C/EC
+
EA-NT-IN
NC
NO
-
NC
C
+
-
+