E-Flex Room Controller 1

••••

2

••••

3

TM

 

Installation G

uide F675

 

F675 R1.02 Lehigh Electric Products Co. 6265 Hamilton Blvd., Allentown, Pa. 18106    Tel: 610-395-3386   www.lehighdim.com 
 

Input Connections: 

DO NOT CONNECT the 24V between two or more room controllers sharing same control signals. However you must connect the COM signal. 

 
Occupancy Input 

 

Push-in spring connection, #24-16 AWG wires, and strip 
length – 3/16 in. 

 
 
 
 

 

Daylight Input  

 

Push-in spring connection, #24-16 AWG wires, and strip 
length – 3/16 in

 
 
 

 

Contact Closure 

 

Push-in spring connection, #24-16 AWG wires, and strip 
length – 3/16 in. 

 

 

 

FlexNet Wiring

See information below. 

Note:  End of line devices are terminated using slide switch. 

 

 
FlexNet Link Wiring 

FlexNet link interconnects up to 100 devices on a single network. Each device is programmed with a unique ID (1-100).  Recommend Alpha 6455 or equivalent. If necessary a 
shielded data cable along with discrete power (18 to 12 AWG) can be used for powered devices.  

 

#24-22 AWG (data), 24-14 AWG (power) wires, strip length – ¼ in., torque – 1.7 lbs.  

 

Cable distance is limited by data wire size and number of devices on a link segment. Using 22 AWG, the total distance is 1000 ft. (300m). Using 24 AWG data the total 
distance is 650 ft. with 100 devices. Number of powered devices will also limit length. Request wiring specification from factory for more detailed information. 

FlexNet Topology and Device Termination 

The diagram above shows daisy-chained link segment wiring and end of line termination between EFRCs. NO T-TAPS or STAR connections ALLOWED.  

 

Sensor to Zone Configuration (SW5) 

 

SW5 Position 

Function 

ON 

OFF 

OCC-Zone 1 

Assigned 

Unassigned 

OCC-Zone 2 

Assigned 

Unassigned 

OCC-Zone 3 

Assigned 

Unassigned 

DAY-Zone 1 

Assigned 

Unassigned 

DAY-Zone 2 

Assigned 

Unassigned 

DAY-Zone 3 

Assigned 

Unassigned 

OCC Mode 

Occupancy 

Vacancy 

OCC Polarity 

Active Low 

Active High (default) 

 
                                                                                                                

        

 

E-Flex Room Controller 1

••••

2

••••

3

TM

 

Installation G

uide F675

 

F675 R1.02 Lehigh Electric Products Co. 6265 Hamilton Blvd., Allentown, Pa. 18106    Tel: 610-395-3386   www.lehighdim.com 
 

 
Setting the FlexNet ID (SW4) ON=1, OFF=0 

Each device on the E-Flex FlexNet network requires a unique ID (1-100). This ID is set using dip switch SW4. This ID is used by an E-Flex room 
controller configuration to determine the source of a sensor to control lighting zones. This ID is also sent in a heartbeat message on FlexNet 
every 4 seconds for device discovery by a gateway. 

 

FlexNet ID 

SW4 

1234 567 

FlexNet ID 

SW4 

1234 567 

FlexNet ID 

SW4 

1234 567 

FlexNet ID 

SW4 

1234 567 

1000 000 

26 

0101 100 

51 

1100 110 

76 

0011 001 

0100 000 

27 

1101 100 

52 

0010 110 

77 

1011 001 

1100 000 

28 

0011 100 

53 

1010 110 

78 

0111 001 

0010 000 

29 

1011 100 

54 

0110 110 

79 

1111 001 

1010 000 

30 

0111 100 

55 

1110 110 

80 

0000 101 

0110 000 

31 

1111 100 

56 

0001 110 

81 

1000 101 

1110 000 

32 

0000 010 

57 

1001 110 

82 

0100 101 

0001 000 

33 

1000 010 

58 

0101 110 

83 

1100 101 

1001 000 

34 

0100 010 

59 

1101 110 

84 

0010 101 

10 

0101 000 

35 

1100 010 

60 

0011 110 

85 

1010 101 

11 

1101 000 

36 

0010 010 

61 

1011 110 

86 

0110 101 

12 

0011 000 

37 

1010 010 

62 

0111 110 

87 

1110 101 

13 

1011 000 

38 

0110 010 

63 

1111 110 

88 

0001 101 

14 

0111 000 

39 

1110 010 

64 

0000 001 

89 

1001 101 

15 

1111 000 

40 

0001 010 

65 

1000 001 

90 

0101 101 

16 

0000 100 

41 

1001 010 

66 

0100 001 

91 

1101 101 

17 

1000 100 

42 

0101 010 

67 

1100 001 

92 

0011 101 

18 

0100 100 

43 

1101 010 

68 

0010 001 

93 

1011 101 

19 

1100 100 

44 

0011 010 

69 

1010 001 

94 

0111 101 

20 

0010 100 

45 

1011 010 

70 

0110 001 

95 

1111 101 

21 

1010 100 

46 

0111 010 

71 

1110 001 

96 

0000 011 

22 

0110 100 

47 

1111 010 

72 

0001 001 

97 

1000 011 

23 

1110 100 

48 

0000 110 

73 

1001 001 

98 

0100 011 

24 

0001 100 

49 

1000 110 

74 

0101 001 

99 

1100 011 

25 

1001 100 

50 

0100 110 

75 

1101 001 

100 

0010 011 

 
Pre-Check 

 

Clean out metal scraps, dust, and debris from the room controller enclosure.

 

 

Inspect low and high voltage wiring for loose connections, bare or damaged insulation.

 

 

Verify that all configuration dip switches and jumpers are set per the installation requirements. 

 

 

Verify that the FlexNet ID is set if the controller is networked on FlexNet and that ONLY the END OF LINE devices are terminated.

 

 

Power Up 

 

Apply power with breaker supplying power to the room controller.

 

 

Test each contact input and ensure the configured relays respond as expected and the relay status LEDs track the response.

 

 
Emergency Test 

All emergency lighting systems should be tested monthly.  This is a short functional test in accordance with BS EN 50172:2004 / BS 5266-
8:2004. To perform this test on the E-Flex room controller press the test button located on the low voltage entry side of the controller. This 
will de-energize the relays, closing the UL924 automatic control relay, and disconnecting the 0-10V dimming common. 

 

Reset Factory Defaults 

Hold SW2 down for 3 seconds until all relay LEDs begin to blink, then release. On release the configuration will be reset to factory defaults. If 

the dip switch settings for sensor zone assignment were overridden by a FlexTool software configuration this step will return control back to 

dip switch settings, i.e. hardware configuration. 

 