E-Flex Room Controller 1

••••

2

••••

3

TM

 

Installation G

uide F675

 

F675 R1.02 Lehigh Electric Products Co. 6265 Hamilton Blvd., Allentown, Pa. 18106    Tel: 610-395-3386   www.lehighdim.com 
 

 

Part Numbers:  

H2861, H2862, H2863 

 

 

H2871, H2872, H2873 

 
Installing: 

1.

 

Prior to installation make sure that you have installed a main circuit breaker cabinet or other input power disconnect. 

2.

 

Mount the room controller on a standard 4 X 4 junction box with a depth of 2 1/8” or greater. It is preferable to use a 3 ½” deep box 
for the UL924 model with emergency circuit. 

3.

 

After connecting the line and load wires, secure the unit to the junction box using two screws. 

 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
Line/Load AC Wiring: 
 

Line In:  HOT – Black, 12 AWG 
 

NEUTRAL – White, 12 AWG 

Loads: 

LOAD1 – Blue, 12 AWG 

 

LOAD2 – Yellow, 12 AWG 

 

LOAD3 – Red, 12 AWG 

UL924 Models 
Emerg:  Emergency Feed – Black, 16 AWG 
 

Emergency Load -  Yellow, 16 AWG

 

 

Warning:

 

RISK OF DEATH OR ELECTRIC SHOCK! 
Before installing input power to the 
controller, make sure upstream source 
of power is off. 

Product Description 

The E-Flex room controller is designed for 120-277V AC, 47-63 Hz installations providing 
controlled switching of up to three zones as well 0-10V dimming with a single circuit feed.  

 

4 X 4 junction box mounted enclosure 

 

Up to three mechanically latching relays with the following ratings: 

o

 

Standard Ballast: 20A @ 120VAC, 277VAC, 347VAC 

o

 

Electronic Ballast: 16A @ 120VAC, 277VAC 

 

Up to three 0-10V outputs with current sink of 100mA and will open upon power 

loss. 

 

Inte24V DC power supply to provide power for sensors and CapT 

stations. 3 unit loads maximum. 

 

Inputs for occupancy and daylight sensors. 

 

Dry contact closure input for timeclock, fire alarm, or demand response. 

 

19 presets plus OFF for up to three zones. 

 

Models with integral UL924 emergency automatic control relay capable of up to 

3A @120/277 VAC. The emergency relay tracks relay 1 and will shunt the 

emergency feed on power loss. 

        

 

E-Flex Room Controller 1

••••

2

••••

3

TM

 

Installation G

uide F675

 

F675 R1.02 Lehigh Electric Products Co. 6265 Hamilton Blvd., Allentown, Pa. 18106    Tel: 610-395-3386   www.lehighdim.com 
 

 
0-10V Outputs 

 

#24-16 AWG wires, strip length – 3/16 in. Follow all national and local codes for separation requirements. 

 

Connect only to NEC Class 2 circuits. 

Connection to non-isolated fixture drivers is not recommended and will VOID warranty

 

Limit distance run for analog control wiring from controller to last driver. Limiting to a voltage drop of .3V maximum will help ensure 

meeting IEC 60929 Annex E standard for minimum 
light level at 1V.  

 
 
 
 
 

 
 
 
 
 
 
 
CapT2 Station Connections: 

 

Note:

 

24V power for CapT stations over Cat5 can only be provided by one source.  
By default, the EFRC does not provide power to the stations. A jumper (JP2) 
on the room controller enables or disables the 24V power to the EFRC RJ45 
connectors.  (See EFRC unit load capability). 

 

CapT2 stations and the E-Flex room controller all have two RJ45 connectors to connect devices together in a system using standard Cat5 

cable. Maximum cable runs 300 ft. 

 

 

 

 

 

 

CapT Power Enable/Disable 

Jumper JP2 is used to enable or disable power to the CapT station RJ45 connectors. The jumper in 
position 1-2 (default) disables power to the connectors. The jumper in position 2-3 (shown) enables 
power to the connectors.  

 
 
 
 

 

To Next EFRC 
or CapT station

CAT5

CAT5

CAT5

CAT5