DESCRIPTION

The Radio Frequency (RF) Plug Load Controller expands the energy savings obtained from traditional occupancy sensing to 

encompass AC receptacles as well as built-in lighting. We accomplish this by providing an RF transmitter (WRC-TX or WRC-TX-LM) 

that connects to your new or existing occupancy sensor, and a switched AC receptacle (WRC-15-x, WRC-20-x) that contains a built-in 

RF receiver. When the RF Signal Pack receives a “vacancy” signal from the sensor, it transmits a message commanding the receptacle 

to turn off. Similarly, when the office becomes occupied, the sensor sends a signal to the RF transmitter and the receptacles turn on. 

Each RF Signal Pack can control up to 16 RF receptacles. A switched feed through allows for control of downstream receptacles from a 

single RF receptacle. Recommended communication range between RF Signal Pack and RF Receptacle is 30 feet. Greater distances 

can be achieved in ideal environments.

RECEPTACLE INSTALLATION INSTRUCTIONS

1.  After removing power as described above, use strip gauge on back of outlet to strip all wires to desired length (if not already stripped).
2.  Attach wires according to the diagram below. Be sure the wires are fastened securely, either by the terminal screws or through the 

back-wire holes in the back of the outlet.

WARNING:

 LOOSELY FASTENED WIRES MAY RESULT IN OUTLET FAILURE AND/OR FIRE HAZARD.

If using terminal screws:

 Terminal screws accept up to #12 AWG wire. Wrap each stripped wire 3/4 turn clockwise under heads 

of screws without overlapping, and tighten securely.

If using back-wire method:

 Back-wire accepts up to a #12 AWG wire. Insert stripped wire between external pressure plate clamp 

and terminal. Tighten securely.

3.  Mount outlet in box using mounting screws supplied. Attach wall plate. Restore power only when finished wiring the entire circuit.

READ & SAVE THESE INSTRUCTIONS! CAUTION:

•  To prevent severe shock or electrocution, always 

turn power OFF at the service panel before 

working with wiring.

•  Use this device with copper or copper-clad wire. 

Do not use with aluminum wire.

•  Must be installed in accordance with National 

and Local electrical codes.

WARNING: I

MPROPER WIRING OF ANY 

ELECTRICAL DEVICE CAN CAUSE SERIOUS 
INJURY OR DEATH. THESE WIRING DEVICES 
SHOULD BE INSTALLED BY AN ELECTRICIAN OR 
OTHER QUALIFIED PERSON.

LIRE ET CONSERVER CES INSTRUCTIONS. 
ATTENTION 

•  Pour éviter tout choc électrique ou une électrocution, 

coupez toujours l’électricité au niveau du panneau 

d’alimentation avant de commencer à câbler.

•  Utilisez ce dispositif avec des fils en cuivre ou 

cuivrés. Ne l’utilisez pas avec des fils en aluminium.

•  Doit être installé conformément aux codes locaux et 

nationaux de l’électricité.

AVERTISSEMENT: 

LE CÂBLAGE INCORRECT  DE 

TOUT DISPOSITIF ÉLECTRIQUE PEUT CAUSER 
DES BLESSURES GRAVES, VOIRE LA MORT. 
CES DISPOSITIFS DE CÂBLAGE DOIVENT ÉTRE 
INSTALLÉS PAR UN ÉLECTRICIEN OU UNE 
PERSONNE QUALIFIÉE.

LEA Y GUARDE ESTAS INSTRUCCIONES. 

PRECAUCIÓN:

•  Para evitar serios electrochoques o electrocución, 

siempre APAGUE el suministro eléctrico en el 

panel de servicio antes de trabajar con los cables.

•  Utilice este dispositivo con alambres de cobre o 

revestidos de cobre. No usar con cables de aluminio.

•  Se debe instalar de acuerdo con los códigos 

eléctricos nacionales y locales.

ADVERTENCIA: 

EL CABLEADO INCORRECTO DE UN 

DISPOSITIVO ELÉCTRICO PUEDE CAUSAR LESIONES 
GRAVES O AÚN LA MUERTE. UN ELECTRICISTA U 
OTRA PERSONA COMPETENTE DEBE INSTALAR 
ESTOS DISPOSITIVOS DE CABLEADO.

15A or 20A

Controlled

Green or Bare Wire

Neutral

15A or 20A

Line

White Screw

Green Screw

Green Screw

125V

125V

250V

White Screw

Not required if both 

faces are controlled

Brass Screw

CONTROLLE

D

CONTROLLE

D

Brass Screw

Brass Screw

CONTROLLE

D

CONTROLLE

D

or

Figure 1