LEGRAND WattStopper LP Series Скачать руководство пользователя страница 10

#

Problem

Test Steps

Next

1

The LV switch 
does not control 
the relay or group.

Is it terminated correctly in the panel? 
See pages 4 & 8.

No – Correct terminations

Yes – Go to next step

Is the 12VDC indicating LED on the C8 
motherboard solid Green?

No – Cycle power to panel; recheck

Yes – Go to next step

Does the board mounted override 
pushbutton control the relay or group?

No – Call tech support

Yes – Go to next step

Disconnect input terminals. 

Does jumping the Red to White input 
terminals turn the relay on and does 
Black to White turn it off?

No – Call tech support

Yes - Verify the LV wiring is not shorted 
and that the switch is operating 
correctly

If using a Group switch, have the relays 
been assigned to the particular group 
using the GS card?

No – Make the necessary assignments 
(refer to page 9)

Yes – Go to next step

2

When I try to 
turn the relay 
off it goes off for 
a second then 
comes back on.

Is this relay scheduled using the “AS 
Manual ON/Auto OFF” or the “AS 
Automatic ON/OFF” scenarios.

No – Go to next Step

Yes – The relay can only be overridden 
OFF during unoccupied periods

Remove any LV switching that is landed 
at the relay input and attempt to turn 
relay ON using the board override 
buttons.

No change in status - Go to next step

Relay functions normally - Verify the 
LV wiring is not shorted and that the 
switch is operating correctly

Move LV relay connection to a different 
point on the RD board and attempt to 
override the relay on.

No change in status - relay needs to be 
replaced - call tech support

Relay functions properly – circuit 
board needs to be replaced - call tech 
support

3

When I try to 
turn the relay on 
it comes on for 
a second then 
comes back off.

Remove any LV switching that is landed 
at the relay input and attempt to turn 
relay ON using the board override 
buttons.

No change in status - Go to next step

Relay functions normally – Verify the 
LV wiring is not shorted and that the 
switch is operating correctly

Move LV relay connection to a different 
point on the RD board and attempt to 
override the relay on.

No change in status - relay needs to be 
replaced - call tech support

Relay functions properly – circuit 
board needs to be replaced - call tech 
support

4

My EM24-A2 
photocell does not 
turn the relay on 
or off.

Is the relay scheduled using the 
“Photocell ON/OFF” or “Photocell and 
Schedule ON/OFF” scenarios?

No – Make the necessary schedule 
changes and test again.

Yes – Go to next step.

Remove the photocell wires or 
connector and jumper from Red to Red.  
Do the relays turn on/off?

Note: If using the “Photocell and 
Schedule ON/OFF” remember to 
adjust the clock time to be within your 
occupied times before doing the jumper. 

No – Call tech Support

Yes – Verify the LV wiring is not shorted 
and that the photocell is operating 
correctly on the roof.

TROUBLESHOOTING

Page 10

Содержание WattStopper LP Series

Страница 1: ...AC P240 Power Supply 240VAC P115 347 Power Supply 115 or 347VAC Load Ratings 120VAC 50 60Hz 20A Tungsten or Ballast 277 347VAC 50 60Hz 20A Ballast 250VAC 1HP Accessory Power Ouput 800mA 24VDC VAC ACR Environmental Maximum Ambient Temperature 60 C Maximum Humidity 5 to 90 RH non condensing UL cUL Listed Installation Wiring Reference ...

Страница 2: ...IONS 1 INTRODUCTION 3 Welcome to the LP Series Lighting Control Panels 3 INSTALLATION 5 Mount the Enclosure 5 Install Interior 6 CONNECT THE LP8 POWER SUPPLY 7 CONNECT LINE VOLTAGE 7 Power Up and Test Relays 7 Confirm Nominal Operation 7 LOW VOLTAGE WIRING 8 Hardwire Low Voltage Switches Optional 8 Install and Wire Exterior Photocell Optional 9 Using Low Voltage Sensors with LP Panels 9 Group Switc...

Страница 3: ...contactors A secure outer cover protects the user from the high voltage area A separate interior enclosure protects the low voltage wiring and components while allowing easy user access to the time clock scheduling controls Most functions are the same for the LP24 as for the LP8 References to LP8 features functions programming and wiring also apply to the LP24 unless specified otherwise If you have...

Страница 4: ...WHITE RELAY PILOT Manual override switch for relays Factory installed jumper provides 24V rectified power to pilot contacts A different voltage 5 24V can be connected to the YELCOM terminal from other equipment looking to monitor relay state pilot contacts For standard use 3 18 Line Neutral To relay as rquired For standard use 2 18 For pilot use 3 18 Light fixture Light fixture Light fixture Notes...

Страница 5: ...nt the Enclosure 1 Place the LP on a sturdy flat horizontal surface 2 Remove the outer cover by removing the cover screws Set it aside 3 Open the interior door containing the clock keypad and display window by pulling up the two black plastic self retained pop fasteners on the left side 4 Remove the panel interior assembly a Remove the washer and nut that attaches the transformer mounting assembly ...

Страница 6: ...ne and low voltage wiring compartments Install Interior Do not reinstall the interior until after the exterior enclosure has been securely mounted to the wall and the conduit wiring holes have been drilled or knocked out 1 Place the interior in the enclosure 2 Align the interior with the studs provided in the enclosure 3 Hold the interior in place while you pull up on the black self retaining pop ...

Страница 7: ... relay 4 Apply power to the relays 5 Being careful not to touch any line voltage wiring toggle each relay on off again and confirm that each relay controls the appropriate load Confirm Nominal Operation With power applied to the LP8 panel there should be two 2 green LED indicators glowing on the power supply card in the lower left corner of the panel And there should be six 6 green LED indicators gl...

Страница 8: ...rd See page 9 Figure 3 Low voltage switch and sensor wiring R B Y W 2 WIRE MAINTAINED CONTACT R to B JUMPER B to W JUMPER 2 WIRE MOMENTARY PUSH BUTTON STANDARD 3 WIRE MOMENTARY STANDARD 3 WIRE MAINTAINED R B Y W RED WHITE RED WHITE BLACK WHITE RED BLACK WHITE RED R B Y W R B Y W R B Y W OCCUPANCY SENSOR or INDOOR PHOTOCELL BLACK BLUE RED Blue Black Red White 24VDC 24VR 24VAC COMMON CONTROL 24VDC R...

Страница 9: ...oup Switching card press and hold the Group push button for several seconds The red group LED and the LEDs for relays currently controlled by that input will begin to flash 2 On each Relay Driver card select the relays to be controlled If a relay was previously Smartwired to the group input selected the LED flashes otherwise the LED is off Press the associated Relay Control Button to add delete that...

Страница 10: ...rted and that the switch is operating correctly Move LV relay connection to a different point on the RD board and attempt to override the relay on No change in status relay needs to be replaced call tech support Relay functions properly circuit board needs to be replaced call tech support 3 When I try to turn the relay on it comes on for a second then comes back off Remove any LV switching that is...

Страница 11: ...you entering ON OFF times using the 24 hour format No Using the 24 hour format make the necessary scheduling corrections Yes Refer to the Spanning Midnight With A Schedule section of the User s Guide and make the necessary scheduling corrections 7 I need to remove a sensor from the system Once a sensor has been connected to a relay driver or group switch card low voltage input the input will remai...

Страница 12: ...A2 Low voltage exterior photocell AS 100 Automatic control switch 120 277VAC 50 60Hz LVS 1 Standard momentary toggle switch RS2 3x Two button low voltage momentary switch L1S Single button low voltage architectural design toggle switch LxS Multi button low voltage architectural design toggle switch DCC2 Low voltage momentary switch Miro Decorator style with LED Multiple options available such as c...

Отзывы: