IMPORTANT INSTALLATION INFORMATION
To ensure a successful installation and startup of a wireless system, the following steps must be taken by the
installing contractor.
Failure to document all device address and locations may delay completion of startup
and result in additional startup charges.
Key Requirement:
Document
every
Device’s MAC Address (at least the last 4 alphanumeric characters). An
additional MAC address label is included for the installer to use on a floor plan map. The last four characters are
repeated in a larger font, in bold. Keep this document so that the commissioning tech has access at a later date.
SETTING UP A ROOM NETWORK BY PAIRING DEVICES
Pair wireless devices to a plug load controller to create an individual room network and enable Plug N’ Go operation.
Device pairing can be done by using Push-to-Pair (PtP) mode on the plug load controller and all other wireless devices, or by using the
DLM Config App.
To pair devices in a network, they must all have the same wireless channel and Network ID. By default the channel is 15 and the
Network ID is 1. Using Push-to-Pair mode, the Network ID for all devices being paired is migrated to a new number, so that only those
devices communicate with each other. The channel number will remain at 15.
NOTE:
LMCS-100 software, version 4.7 or later can also be used to pair devices. However, LMCS-100 requires use of an LMBR-650.
Using LMCS, it is possible to change the channel as well as Network ID.
SET UP A ROOM NETWORK USING PUSH-TO-PAIR MODE
Push-to-Pair in a room with multiple wireless room controllers and one or more LMPL-611-20Ms
In a room with multiple loads, it is likely there will be both an LMRC wireless room controller and a plug
load controller. Or, there may be more than one LMPL-611-20M. They can all be paired to the same
room network, allowing the scene switch to set each load to different levels per scene. One of the
controllers will become the master, determining the Network ID and channel settings for all the devices
in the network.
NOTE:
Once you enter PtP mode on the plug load controller, a three minute timer begins. If the Config
button on any device in the room is pressed, the timer resets and begins the three minute
countdown again. If no Config button is pressed within three minutes, the plug load controller
will exit PtP mode.
1.
Enter wireless Push-to-Pair (PtP) mode
on all room/plug load controllers.
Press the Config
button three times on each LMRC-611 or LMPL-611 to put them all in PtP mode. The green LEDs
will flash on all room controllers. The
first
room controller placed into PtP will become the
master
.
Config button
Load button
Examples of labels
MOUNTING AND WIRING
The LMPL-611-20M room controller can be mounted external to any junction box with 1/2”
knockouts, and can be mounted in a plenum space.
If mounting two controllers on the same junctions box,
you must maintain a minimum of
6” between each room controller
. This means mounting the LMRC on opposite ends.
The relay is rated for a load of up to 20A. The Line (Black) and both Load (Red, and Black with White Stripe) wires are #12 AWG. The
Neutral (White) wiring is #18 AWG.
WARNING:
TURN THE
POWER OFF AT THE
CIRCUIT BREAKER
BEFORE WIRING.
Line Voltage In
To Load
Less Signal
Strength
More Signal
Strength
IMPORTANT:
CEILING MOUNTED LMRC
s
MUST BE MOUNTED WITH THE LABEL
SIDE FACING DOWN TOWARDS THE FLOOR TO INCREASE COMMUNICATION
PERFORMANCE WITH OTHER WIRELESS SWITCH AND SENSOR DEVICES.
LMRC
s
MOUNTED ON THE WALL MUST HAVE THE UNIT LABEL FACE INTO THE ROOM.
LMPL-611-20M
Line
Voltage
Deep J-Box
Loads
Red wire to Switched Receptacle
Line/Hot
Black wire
Neutral
White wire
Switched
Receptacle
Black wire w/white stripe to Unswitched Receptacle
Unswitched
Receptacle
Ground
Ground
Distance Recommendations for LMPL-611-20M:
6” minimum and 100’ maximum between this device and any other
LMRC-6xx, LMPL-6xx, or LMBC-650
10’ minimum 100’ maximum between this device and an LMBR-650
30’ maximum between this device and a mobile device