PLUG N’ GO OPERATION (PNG)

The plug load circuit connected to the LMPL-201 is automatically controlled 

by all occupancy sensors on the DLM local network. After the last occupancy 

sensor’s time delay expires, the LMPL-201 shuts 

OFF

 the switched 

receptacle circuit.

Load Control Arbitration

To take full advantage of automatic PnG configuration, review these simple rules about load control 

arbitration.
After the room controllers are connected to the DLM Local Network and powered up they automatically 

negotiate to determine which controller becomes the 

Master

 and the load numbers for each relay on the 

DLM Local Network.
The 

Master

 is the controller with the highest serial number. The LMPL-201 has one load relay.

In a DLM local network with only LMPL-201 plug load room controllers, the LMPL-201 with the highest serial 

number is the 

Master

, carrying Load 1. The next highest serial number would have Load 2 and so forth.

UNIT ADJUSTMENT - PUSH N’ LEARN (PNL)

Load Selection Procedure

A configuration button (Config) allows access to our patented Push n’ Learn™ technology to change binding relationships between 

sensors, switches and loads.

Step 1 Enter Push n’ Learn

Press and hold the Config button (on any DLM device) for 3 seconds.

The red LED on the LMPL-201 begins to blink. When you release the button, the red LEDs on other 

communicating devices connected to the DLM Local Network begin to blink. They continue to blink until you 

exit PnL mode.
All loads in the room turn 

OFF

 immediately after entering PnL, then one load will turn 

ON

. This is Load #1, 

which is bound to all occupancy sensors on the DLM local network as part of the  Plug n’ Go factory default 

setting. 

All switch buttons and sensors that are bound to this load have their blue LED solid ON.

Step 2 Load selection

Press and release the Config button to step through the loads connected to the DLM Local Network. As each load turns 

ON

 note the 

devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices are currently bound to the load that is 

ON

. The blue LED on the room controller or plug load controller connected to the load is also lit.

•  To 

unbind

 a switch button from a load, press the switch button while its blue LED is 

ON

 bright. The blue LED goes dim to indicate 

the button no longer controls the load that is currently 

ON

.

•  To 

unbind

 an occupancy sensor, press the up (

) or down (

) adjustment button while its blue LED is 

ON

. The blue LED turns 

OFF

 to indicate the sensor no longer controls the load that is currently 

ON

•  Pressing the switch button or sensor up (

) or down (

) again while the load is 

ON

 

rebinds

 the load to the button or sensor and 

the blue LED illuminates brightly.

Step 3 Exit Push n’ Learn

Press and hold the 

Config

 button until the red LED turns 

OFF

, approximately 3 seconds.

MOUNTING THE CONTROLLER

The plug load room 

controller mounts as the 

cover for a four square 

deep junction box. It is 

equipped with a lash and 

hook to hang the controller 

from a j-box cover tab 

while connecting the 

line voltage wires. After 

securely connecting the 

wires, unhook the lash 

from the j-box and secure 

the controller to the j-box 

cover tabs using two screws. 

Remove rubber jack covers to use RJ45 receptacles. 

Leave covers in place for all unused receptacles.

Use a 4”x 4”x 2 1/8” 

deep  (minimum)  box                          

 

Blue LED 

ON

 when switched 

receptacle circuit is 

ON

.

Load button: 

Press & release to turn the 

switched receptacle 

ON/OFF

.

Hook

Lash

4” square

deep

J-box

0341373638

Serial 

Number

Plug Load

Controller

Load

Control

LMPL-201

0429928526

Master

0341373638

LMPL-201

1

0429817004

2

Config button & red LED

ATTACHING LMRJ LOW VOLTAGE CABLES

Содержание Wattstopper LMPL-201

Страница 1: ...n accordance with all applicable regulations local and NEC codes Wire connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring...

Страница 2: ...nd to this load have their blue LED solid ON Step 2 Load selection Press and release the Config button to step through the loads connected to the DLM Local Network As each load turns ON note the devic...

Страница 3: ...e guide d installation du syst me DLM fourni avec les combinateurs Wattstopper et aussi disponible au www legrand us wattstopper L installation doit tre effectu e conform ment tous les r glements ains...

Страница 4: ...quement celui qui devient le contr leur principal et les nombres de charges pour chaque relais du r seau local DLM Le contr leur principal est celui qui poss de le num ro de s rie le plus lev Le LMPL...

Страница 5: ...ntre le dispositif et le s combinateur s Les mauvais clairages et charges de prise sont contr l s 1 Configurez les boutons d interrupteur et les d tecteurs de mani re contr ler les charges d sir es en...

Страница 6: ...je de la red local DLM Cables LMRJ Serie LMPL o LMRC Cargas Cable rojo a recept culo conmutado Cable de l nea negra vivo Cable neutro blanco Cable tierra verde Recept culo conmutado Cable negro con ra...

Страница 7: ...PnL a continuaci n se ACTIVAR una carga Esta es la carga N 1 que est vinculada con todos los sensores de ocupaci n de la red local DLM seg n la configuraci n predeterminada de f brica de Plug n Go To...

Страница 8: ...nsabilidades por parte de Wattstopper por da os consecuentes que se deriven o est n relacionados con el uso o el rendimiento de este producto u otros da os indirectos con respecto a la p rdida de prop...

Отзывы: