LEGRAND Wattstopper LMDX-100 Скачать руководство пользователя страница 3

3

FACTORY PRE-SET OPERATION

Sensor Parameters

T-DELAY 

                                     Time Delay 

20 minutes

Passive Infrared 

Sensitivty

90%

Ultrasonic 
Sensitivity

70%

W-T

Walk Through

OFF

TRIG

Initial Occupancy

PIR and    

Ultrasonic

RETRIG

Maintain Occupancy

PIR or  

Ultrasonic

Load Parameters

Load 1

 

Loads 2-8 or more** 

  

 

Plug Load

ON Mode

Operation*

AUTO-ON

MANUAL-ON
if switch is used.
AUTO-ON
if switch is not used.

AUTO-ON

Blink Warning

OFF

OFF

OFF

Daylighting

ON

OFF

OFF

TROUBLESHOOTING

Loads do not operate as expected.

LEDs don’t light, display is off.

1.  Check to see that the sensor is connected to the DLM local Network.
2.  Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor 

location. If the device does not power up, 24VDC is not present.
•  Check the high voltage connections to the room controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local 

Network connections between the sensor and the room controller.

The wrong lights are controlled.

1.  Configure the sensor to control the desired lights using the Push n’ Learn adjustment 

procedure.

LEDs turn ON and OFF but load 

doesn’t switch.

1.  Make sure device is not in PnL.
2.  Check load connections to room controller.

* Auto-OFF is enabled according to the sensor Time Delay 

when a sensor is bound to the load, regardless of whether the 

load was turned on automatically with occupancy or manually 

using a switch.
** Max 8 loads using LMRC-100 series room controllers.