FACTORY PRE-SET OPERATION
Sensor Parameters
T-DELAY
Time Delay
20 minutes
Passive Infrared
Sensitivty
90%
Ultrasonic
Sensitivity
70%
W-T
Walk Through
OFF
TRIG
Initial Occupancy
PIR and
Ultrasonic
RETRIG
Maintain Occupancy
PIR or
Ultrasonic
Load Parameters
Load 1
Loads 2-8 or more**
Plug Load
ON Mode
Operation*
AUTO-ON
MANUAL-ON
if switch is used.
AUTO-ON
if switch is not used.
AUTO-ON
Blink Warning
OFF
OFF
OFF
Daylighting
ON
OFF
OFF
TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t light, display is off.
1. Check to see that the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor
location. If the device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local
Network connections between the sensor and the room controller.
The wrong lights are controlled.
1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment
procedure.
LEDs turn ON and OFF but load
doesn’t switch.
1. Make sure device is not in PnL.
2. Check load connections to room controller.
* Auto-OFF is enabled according to the sensor Time Delay
when a sensor is bound to the load, regardless of whether the
load was turned on automatically with occupancy or manually
using a switch.
** Max 8 loads using LMRC-100 series room controllers.