Wattstopper
®
DLM Dual Technology Corner Mount Occupancy Sensor
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24598 – 09/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMDX-100
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
LMDX-100 -U is BAA and TAA compliant (Product produced in the U.S.)
SPECIFICATIONS
Voltage .............................................................................. 24VDC
Current Consumption ...........................................................20mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network ........................ RJ-45 plug
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000’ max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
This unit is pre-set for Plug n’ Go™ operation, adjustment is
optional.
For full operational details, adjustment and more features of the product, see the
DLM System Installation Guide provided with Wattstopper room controllers, and
also available at www.legrand.us/wattstopper.
Installation shall be in accordance with all applicable regulations, local and
NEC codes.
Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a Class 2 power
source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.
SENSOR PLACEMENT
Sensor
30'
30'
Sensor
Ceiling
COVERAGE PATTERN
Coverages shown are maximum and represent half-step walking motion.
Side view
10’
Top view
40
’
0 7’ 15’ 25’
45’
PIR
coverage
45ft.
Ultrasonic
coverage
28ft.
CAUTION:
TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT
– IT MAY
DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.