LEGRAND Wattstopper LMDX-100 Скачать руководство пользователя страница 1

Wattstopper

 

®

DLM Dual Technology Corner Mount Occupancy Sensor

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24598 – 09/16  rev. 1

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMDX-100

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMDX-100 -U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltage .............................................................................. 24VDC
Current Consumption ...........................................................20mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network ........................ RJ-45 plug
DLM Local Network characteristics when using LMRC-11x/2xx 

room controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ................................................. For Indoor Use Only
 

Operating Temperature .................32° to 131°F (0° to 55°C)

 

Storage Temperature ...................23° to 176°F (-5° to 80°C)

 

Relative Humidity .......................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, adjustment is 

optional.

For full operational details, adjustment and more features of the product, see the 

DLM System Installation Guide provided with Wattstopper room controllers, and 

also available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable regulations, local and 

NEC codes. 

Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 power 

source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.

SENSOR PLACEMENT

Sensor

30'

30'

Sensor

Ceiling

COVERAGE PATTERN

Coverages shown are maximum and represent half-step walking motion. 

Side view

10’

Top view

40

0 7’ 15’ 25’

45’

PIR

coverage

45ft.

Ultrasonic

coverage

28ft.

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 – IT MAY 

DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.