LEGRAND Wattstopper LMDC-100 Скачать руководство пользователя страница 1

Wattstopper

 

®

DLM Dual Technology Ceiling Mount Occupancy Sensor (version 4)
DLM Double Technologie Montage au Plafond Détecteur de Présence (v4)
DLM Sensor de Ocupación con Doble Tecnología y Montaje en Techo (v4)

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 31781 – 12/21  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMDC-100

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMDC-100-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltage .....................................................................................24VDC
Current Consumption ................................................................. 20mA
Power Supply ........................................ Wattstopper Room Controller
Connection to the DLM Local Network ........................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx room 

controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x series  

 

and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ........................................................ For Indoor Use Only
 

Operating Temperature ........................32° to 131°F (0° to 55°C)

 

Storage Temperature ......................... 23° to 176°F (-5° to 80°C)

 

Relative Humidity ..............................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, adjustment is 

optional.

For full operational details, adjustment and more features of the 

product, see the DLM System Installation Guide provided with 

Wattstopper room controllers, and also available at  

www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable 

regulations, local and NEC codes. 

Wire connections shall be 

rated suitable for the wire size (lead and building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a 

Class 2 power source only. Do not reclassify and install as Class 

1, or Power and Lighting Wiring.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)This device may not cause 

harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

NOTE: 

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. 

These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial 

environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the 

instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to 

cause harmful interference in which case the user will be required to correct the interference at his own expense.

SENSOR PLACEMENT (10’ MAX. HEIGHT)

Sensor   Capteur

25'

7.6m

25'  7.6m

Strong air

supply

6’

Sensor

Mount sensor at least 6’ away from air supply.

Avoid obstacles that block sensor’s line-of-sight.

Pendant

fixture

Содержание Wattstopper LMDC-100

Страница 1: ...attstopper room controllers and also available at www legrand us wattstopper Installation shall be in accordance with all applicable regulations local and NEC codes Wire connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring To be connected to a Class 2 power source only Do not reclassify and install as Class 1 or Power and...

Страница 2: ... ceiling tile WARNING A junction box used for sensor installation must not contain any Class 1 Class 3 or other power or lighting line voltage circuits CONNECTIVITY The illustrations below show examples of free topology wiring The LMDC 100 communicates to all other Digital Lighting Management devices connected to the low voltage DLM Local Network regardless of their position on the DLM Local Netwo...

Страница 3: ...y selected setting 3 4 or 5 times also indicated by the red LED blink pattern NOTE You must press the CONFIGURE button the same number of times to exit edit mode For example if you press the button 4 times to edit PIR Sensitivity pressing 3 times will not exit edit mode After exiting edit mode you may repeat from step 2 to edit additional parameters Red LED PIR Detect Push n Learn Blue LED Ultraso...

Страница 4: ...2 Check for 24VDC input to the sensor Plug in a different DLM device at the sensor location If the device does not power up 24VDC is not present Check the high voltage connections to the room controller If high voltage connections are good and high voltage is present recheck DLM local Network connections between the sensor and the room controller The wrong lights are controlled 1 Configure the sen...

Страница 5: ...e 1 ou en tant que fil d alimentation ou d éclairage Ce dispositif est conforme à la section 15 des règlements de la FCC On peut s en servir sous réserve des deux conditiond suivantes 1 Ce dispositif ne provoque pas d interférences nuisibles 2 Il doit être en mesure d accepter toute interférence reçue y compris les interférences qui peuvent causer un fonctionnement indésirable REMARQUE Ce matériel...

Страница 6: ... neutre Câble rouge vers charge A 1 Câble jaune vers charge B 2 LMRC 102 Régulateur d ambiance Boîte de jonction Détecteur de présence monté au plafond Interrupteur Vers charge Partie arrière 10cm Octogonale Boîte de jonction au moins 4cm de profondeur Couvercle frontal Plafond Trou percé au plafond Câble LMRJ Câble LMRJ Clips ressort 2 Vis Pour les applications exigeant le respect des normes plén...

Страница 7: ...0 minutes et n augmentera pas de deux à 30 minutes Après cela chaque pression supplémentaire sur un bouton augmente la valeur 5 Pour revenir au fonctionnement normal appuyez sur le bouton CONFIGURER le nombre de fois correspondant au réglage actuellement sélectionné 3 4 ou 5 fois également indiqué par le motif de clignotement de la DEL rouge REMARQUE Vous devez appuyer sur le bouton CONFIGURE le m...

Страница 8: ...ambiance Si les raccords haute tension sont corrects et que la haute tension passe bien vérifier de nouveau les branchements au réseau DLM local entre le capteur et le régulateur d ambiance Les éclairages pilotés ne sont pas les bons 1 Configurer le capteur pour qu il pilote les éclairages souhaités à l aide de la procédure de réglage Push n Learn Les LED s allument et s éteignent mais la charge n...

Страница 9: ...tale como Clase 1 ni con circuitos de alimentación e iluminación Este dispositivo cumple con la parte 15 de las reglas de la FCC La Operación está sujeta a las dos condiciones siguientes 1 Este dispositivo no puede causar interferencias perjuduciales y 2 este dispositivo debe aceptar cualquier interferencia recibida incluidas las interferencias que puedan causar una operación no deseada NOTA Este ...

Страница 10: ...Blanco Cable neutro Cable rojo a carga A 1 Cable amarillo a carga B 2 LMRC 102 Controlador de habitación Caja de conexiones Sensor de ocupación de montaje en techo Interruptor Hacia la carga Alojamiento trasero 10cm Caja Octogonal de conexiones al menos 4cm de profundidad Cubierta frontal Cielo raso Orificio de techo Cable LMRJ Cable LMRJ Abrazaderas de resorte 2 Tornillos Para aplicaciones que re...

Страница 11: ...LOAD dos veces cambiará a 10 minutos no aumentará en dos a 30 minutos Después de eso cada vez que se presiona un botón adicional aumenta el valor 5 Para volver al funcionamiento normal presione el botón CONFIGURE el número de veces que corresponda al ajuste seleccionado actualmente 3 4 o 5 veces también indicado por el patrón de parpadeo del LED rojo NOTA Debe presionar el botón CONFIGURE la misma...

Страница 12: ...C al sensor Conecte un dispositivo DLM diferente en la ubicación del sensor Si el dispositivo no se enciende los 24 V de CC no están presentes Revise las conexiones de alto voltaje al controlador de la habitación Si las conexiones de alto voltaje son correctas y hay alto voltaje vuelva a revisar las conexiones de red local DLM entre el sensor y el controlador de la habitación Se controlan las luce...

Отзывы: