LEGRAND Wattstopper LMCT-100-2 Скачать руководство пользователя страница 20

20

The Load Shed utility determines how the loads in the room will 

respond to a Load Shed command via BACnet.

L o a d   S h e d   M e n u

SHEDS ALL ROOM LOADS!

S h e d   t o   L e v e l :  

< 6 5 >

T i m e o u t   M i n u t e s :  

< 3 0 >

M o d e :  

< N o   O v e r r i d e >

    SEND                  DONE

Shed to Level

The maximum level the load will go to when it receives a Load 

Shed command. If the load is currently at a higher level, it will 

reduce to this amount. If it is currently at a lower level, it will 

remain at that level. Once the load shed is relinquished, the load 

will go to the level determined by the next highest priority. This 

could be the setting of a switch such as a scene switch, or the 

level set as part of a schedule.
Available values: 5% to 100%, in 5 % increments, and Load. If 

set to Load, the load will use the individual Shed to Level that 

can be set for a specific load. LMCS-100 software is required to 

access that parameter.

Timeout Minutes

This limits the amount of time after the Load Shed occurs 

before relinquishing the load shed. Available values are 5 to 250 

minutes in 5 minute increments, and Off. If set to Off, the load 

shed is not relinquished until a command is received via BACnet 

to do so.

Mode

This parameter has three possible values:

• 

No Override

 – Initiates the load shed, but does not allow 

users to adjust the lighting levels

• 

Override

 – Initiates the load shed, but allows users to 

adjust the lighting levels

• 

Disable

 – Prevents the load from responding to the load 

shed command.

Once you have edited the parameters as needed, choose 

SEND

 

and press Select, then point at an IR receiver and press Select 

again. To exit , press 

DONE

.

Status

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

A panel or bridge is required to use this option. It provides 

status information on loads, groups, photosensors, and sensors 

connected to the panel or bridge.
An additional screen containing status information specific to 

panels is also available from the 

Panel Setup

 screen. See 

“Panel Status” on page 24

.

Load Status

S t a t u s   –   P a n e l

L o a d   S t a t u s

G r o u p   S t a t u s

L i g h t   L e v e l

O c c u p a n c y   S e n s o r s

  

   

D o n e

This set of screens displays details about each load in the panel, 

as well as any loads in connected room controllers.

Smart Wire

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

S m a r t W i r e   M e n u

S t a r t   S m a r t W i r e

S t o p   S m a r t W i r e

  

   

D o n e

The Smartwire feature is used to configure LMSW buttons and 

DLM occupancy sensors to control relays in the LILM series 

Lighting Integrator panel. 
With 

Start Smartwire

 selected, point the LMCT-100-2 at the 

switch or sensor to be programmed and press Select to enter 

the Smartwire mode. Select Stop Smartwire and point at the 

device to exit the Smartwire mode. 

NOTE: 

The LILM panels are no longer sold, so this option is for 

legacy support only.

Identify Devices

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

       Identify Device 01-06

LMRC-102     0461385398
HW: 10 Year         14 Week

HW Version:                008

FW Version:          005.025

    

NEXT

    PRIOR    DONE  

Identify Devices provides access to service information for 

individual DLM devices in the room. Note that this feature only 

works with DLM room devices shipped after January 2012.
The room controller (or panel) assigns a number to each device 

when connection between devices is first established. The 

NEXT

 and 

PRIOR

 buttons will cycle through the devices in that 

order. The number in the upper right corner shows the device 

number and total number of devices. In the example above the 

room controller is device 1 of 6 in the local network. The room 

controller (or panel) will always be the first device.

Force System into PnG

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

F o r c e   S y s t e m   i n t o   P n G

I f   y o u   a r e   s u r e   y o u

w a n t   t o   f o r c e   a   P n G

P o i n t   t o   A N Y   I R

e n a b l e d   d e v i c e ,   a n d

P r e s s   ‘ S e l e c t ’

Forcing a PnG will reset the room devices back to their original 

Plug and Go states and the room will immediately initiate a fresh 

Plug and Go sequence.

Room Mode

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

S e t   R o o m   M o d e

S e l e c t   e i t h e r   N o r m a l

H o u r s   o r   A f t e r   H o u r s

N o r m a l   H r s

        A f t e r   H r s

Room Mode will force the mode of the room into the After Hours 

or Normal Hours mode. Since sensor settings changed while in 

After Hours mode will apply only when the room is in that state, 

switching to After Hours mode will allow testing of the settings 

when a room is usually in Normal Hours. Be sure to return the 

room to the proper mode before exiting.

Load Shed

U t i l i t i e s   M e n u

S m a r t W i r e

I d e n t i f y   D e v i c e s

F o r c e   S y s t e m   i n t o   P n G

R o o m   M o d e

L o a d   S h e d

S t a t u s

  

   

D o n e

Содержание Wattstopper LMCT-100-2

Страница 1: ...7 Bind 7 Next 7 Exit 7 Daylighting Configuration 7 Specific Photosensor 7 Search Photosensor 7 Zone Setup LMLS400 LMLS 600 Only 8 Zone Setup LMLS 500 Only 9 Calibration LMLS 400 Only 10 Calibration LMLS 500 Only 11 Calibration LMLS 600 Only 11 Zone Settings LMLS 400 Only 12 Zone Settings LMLS 500 Only 13 Zone Settings LMLS 600 Only 13 Switched Bi Level or Tri Level 13 Advanced Settings LMLS 400 on...

Страница 2: ...l Programming 23 Schedules 23 Holidays 24 Panel Status 24 Group Setup 24 Group Loads 24 Using the Smartwire Feature 25 Defining Custom Group Parameters 25 Group Occupancy Sensor Settings 26 Group Dark Light Events 26 Troubleshooting 27 LMLS 400 LMLS 500 Daylighting Control 27 Appendix Updating the Firmware in the LMCT 100 2 29 Installing Firmware in the LMCT 100 2 29 ...

Страница 3: ... can change any of the DLM occupancy sensor parameters such as sensitivity time delay and more With the LMCT 100 2 you can also change load configurations without any new wiring The LMCT 100 2 can change dimming system options such as scene assignments fade rates and other options not available through the standard user interface Additionally the LMCT 100 2 can be used for initial configuration of...

Страница 4: ...on in the sensor Ultrasonic sensors only Trigger Retrigger Mode Dual Tech Sensors only Trigger Indicates whether to use PIR Ultrasonic Either or Both technologies for initial detection of occupancy For Either the sensor will register occupancy if either of the two technologies senses movement whereas for Both both technologies must detect movement Retrigger Indicates whether to use PIR Ultrasonic ...

Страница 5: ... Yes NH Delay 1 Min AH Delay 2 Min NEXT PRIOR SEND DONE After selecting the Analog Occ Sensors option point the LMCT 100 2 at any IR enabled device in the room There must be an LMIO 201 connected with an analog sensor wired correctly to the LMIO 201 or you will receive an error If the LMIO 201 is connected and wired properly and you still receive an error press the Config button on the LMIO 201 Th...

Страница 6: ...irst Load Config PnL Load 1 Operation Auto On Blink Disable Load Type NonDim SEND BIND NEXT EXIT Push to highlight NEXT and push the SELECT button to turn ON the next load and view its settings Once the Load is selected you can bind a button to the load by pressing that button Use the BIND option on the screen to bind sensors to a load this prevents having to access the button on a sensor placed i...

Страница 7: ...rs in high bay applications it is important to stand directly underneath the sensor with the LMCT 100 2 held in a vertical orientation pointed at the bottom of the sensor In some cases direct communications between the LMCT 100 2 and the LMLS 600 may be difficult to achieve due to interference from very high ambient light when looking up from direct sunlight high intensity fluorescent fixtures e g...

Страница 8: ...ing 2 load circuits Load 1 OFF Off 0 Med 50 Max 100 Load 2 OFF Load 1 ON Load 2 OFF Load 1 ON Load 2 ON Tri Level Tri level mode provides four light levels within the daylighting zone controlled by the photosensor by using 2 load circuits Off 0 Low 33 High 66 Max 100 Load 1 OFF Load 2 OFF Load 1 OFF Load 2 ON Load 1 ON Load 2 OFF Load 1 ON Load 2 ON Dimmed Dimmed mode provides continuous dimming w...

Страница 9: ... Control Mode Zone Setup LMLS 5 0 0 Number of Zo nes 3 CONT IN U E Press Left Right arrow to select the number of Zones 1 2 or 3 Point to A ny IR enabled d evi ce o n the n et w o rk Press Sel ect Choose the numb er o f Daylight i ng Zo nes Zone Setup LMLS 500 Zone 1 Bi Level Zone 2 Switched Zone 3 Tri Level CONTINUE Pick a control type for ALL Zones Zone Setup LMLS 5 0 0 Bi L evel NEXT PRIOR D ON...

Страница 10: ...changes based on the Operating Mode Switched Bi Level and Tri Level Choose a reference location within the daylighting zone that is most likely to have the lowest light level when day lit and is located farthest from the window Calibrating LMLS 400 Desired Light Level at the workplane 50fc Actual Light Level at at the workplane 35fc SEND To set the On and Off Setpoints automatically to best match ...

Страница 11: ...s the skylight area remain free of any obstructions and that no changes occur including human foot traffic within the cone of view of the closed loop sensor Please clear the area before starting the Automatic Calibration and wait for the calibration completion when the blue LED stops flashing once every 4 seconds before reentering the area Daylighting Confi g LMLS 400 Night Setup Night Setpoint Sa...

Страница 12: ... a t io n Zone Se t t in g s Adva n c e d Se t t in g s Con t ro l Mo d e Zone Settings When Zone Settings is selected one of two screens is displayed depending on the Operation Mode of the device Switched Bi Level or Tri Level or Dimmed Switched Bi Level or Tri Level Daylighting LMLS 400 Bi Level SEND ON Setpoint OFF Setpoint ON Time Delay OFF Time Delay 7 5fc 11fc 20sec 10min This heading differ...

Страница 13: ... 3 min to 30 min Send To send the changed settings to the LMLS 500 select SEND point the LMCT 100 2 at an IR enabled device and press Select Dimmed Daylighting LMLS 500 SEND NEXT ZONE DONE Setpoint Ramp Up Ramp Down Cut Off Delay 50fc 20 sec 2 sec 10min Zone 1 Dimmed Setpoint The desired light level at the task per zone To determine the correct dimming level for any given photocell reading it calc...

Страница 14: ... details However the LMLS 500 has a NEXT option Select that option to display the following screen Daylighting LMLS 500 PRIOR DR Z1 300 fc 300 fc DR Z2 300 fc 300 fc DR Z3 300 fc 300 fc EL Z1 300 0 fc EL Z2 300 0 fc EL Z3 300 0 fc This screen displays the current readings of the Daylight Ratio DR and Electric Light contribution EL for each zone OFF Setpoint The target illuminance level above which...

Страница 15: ... of all of the controlled electric lights as seen in the closed loop down looking sensor Daylight Ratio Shows the latest average ratio between the daylight contribution seen in the closed loop down looking sensor and that measured by the open loop up looking sensor Force Open Loop When set to Yes this parameter causes the sensor to always reference the Open Loop sensor during control operations an...

Страница 16: ... loads bound to the button Any bound load ON LED ON Bound loads OFF LED OFF Bound loads ON LED ON ToggleNT mode is intended for use when the button is assigned to a Group For details on this mode see the section on Group Button Parameters on page 17 Fade On Fade Off Fade On and Fade Off determines the time that it takes for loads bound to this button to reach the target level The fade time default...

Страница 17: ...t level to a scene button by pressing and holding the button for 7 seconds If set to Yes this feature is locked and the user can t change the scene setting Fade On Fade Off Fade On and Fade Off determines how much time it takes for the loads to reach their target levels when this button is pressed The fade time defaults are Use Load s By default all loads in a scene carry a two second ON and OFF f...

Страница 18: ...or fade the load turns ON or OFF The value options are 1 25 51 75 or 100 The default is 51 NOTE For a room controller that does not support dimming the Type will not be selectable and will specify a switched load only Send Next Prior These options function the same as with dimming loads ADJUST LIGHT LEVEL To access the Adjust Light Level option select More when on the initial Home screen to view t...

Страница 19: ...for other devices to determine if its current MAC address is being used by another device If not it will keep the same address but if it is and will assign an unused number between 32 and 127 If you change AutoSet MSTP MAC to No the parameter below changes to you Manual MSTP MAC and you can manually assign an MS TP MAC address instead of having the panel or bridge automatically assign the number T...

Страница 20: ...ify Devices Force System into PnG Room Mode Load Shed Status Done SmartWire Menu Start SmartWire Stop SmartWire Done The Smartwire feature is used to configure LMSW buttons and DLM occupancy sensors to control relays in the LILM series Lighting Integrator panel With Start Smartwire selected point the LMCT 100 2 at the switch or sensor to be programmed and press Select to enter the Smartwire mode S...

Страница 21: ...lay countdown will start When the countdown reaches 0 the blink function re occurs NOTE Blink does not apply when transitioning from After Hours to Normal Hours TDelay NH None TDelay AH 120 min NH AH Tur n Off AH NH Do Nothing Load 2 Properties 2 NEXT PRIOR DONE TDelay NH If a load is commanded to turn ON when the schedule switches to Normal Hours the load will automatically turn OFF after the tim...

Страница 22: ...rn to the Status screen Light Level Li ght L evel 1 f c 301 1 of 2 Level MAC 0373303229 NEXT PRIOR DONE This screen displays the current light level in foot candles registered by an LMIO 301 with an attached photosensor The top line of the display shows the number of LMIO 301s connected to the network The display shows the light level of a single device The second line shows the serial number MAC ...

Страница 23: ... 24 NOTE While bridges can store group data schedules are specific to panels So you can set up groups within a panel and a bridge and then have the panel send schedule events to both its internal groups and an external bridge Schedules 603981210 Schedules Holidays Panel Programming Select Schedules point the LMCT 100 2 at the infrared sensor on the LMRD board and press Select to open the Program S...

Страница 24: ...e SensAutomatic Group Setup LOADS CUSTOM DONE DELETE SEND Group Select the group number Each panel has 99 memory locations for storing group parameters and each bridge has 16 locations Type Select one of the predefined macros see below or select Custom to define the group behavior parameters Next Select LOADS Point the LMCT 100 2 at the infrared sensor on the LMRD board and press Select to open th...

Страница 25: ... is available for bridges as well as panels it is less practical for bridges as it requires you to have easy access to each room controller so you can press the relay switches for individual loads on the room controller Defining Custom Group Parameters If you select a value of Custom for Type on the Group Setup screen then you must select the CUSTOM option on that screen which opens the Group x Cu...

Страница 26: ... Select You return to the Group Setup screen Important You must SEND the settings for an event before selecting another event or those settings will be lost Group Dark Light Events Group Loads Group Occ Sensors Group Dark Light DONE Group Setup LMBC On this set of screens you assign individual dark light events based on sunrise sunset settings or on dark light triggers from a photo sensor connecte...

Страница 27: ...Normal to resume daylighting operation time value of 20 minutes the Dark event will trigger 10 minutes before sunset and the Light event will trigger 10 minutes after sunrise The LMCP User Guide contains a chart shows this example in greater detail Finally you assign a Group for this event to control the relays belonging to that group LMIO 301 Events Contro ller LMIO 301 1 Dark L N Z Li ght Tu r n...

Страница 28: ...ation If the latter complete the commissioning operation first otherwise use a wall switch to turn off the controlled loads to terminate the override Explanation If the blink is faster one flash every second the photosensor is in Test Mode or Demo Mode 1 Test Mode will cancel automatically after five minutes 2 Alternatively it can be turned off by selecting the Control Mode menu from the LMLS 400 ...

Страница 29: ... not be able to upgrade the firmware but there will be no error message saying that the driver is missing Installing Firmware in the LMCT 100 2 Wattstopper support can provide information how to download a copy of the most recent firmware Once that file is saved on your computer take the following steps to install the file 1 Remover the battery cover from the LMCT 100 2 to expose the micro USB jac...

Страница 30: ...lié à la perte de propriété de revenus ou de profits ou aux coûts d enlèvement d installation ou de réinstallation Wattstopper garantiza que sus productos están libres de defectos en materiales y mano de obra por un período de cinco 5 años No existen obligaciones ni responsabilidades por parte de Wattstopper por daños consecuentes que se deriven o estén relacionados con el uso o el rendimiento de ...

Отзывы: