TROUBLESHOOTING

The red LED will flash until both the Day and Night levels are properly adjusted. The Night level must always require more electric light 

output than the Day level. If it does not, the red LED on the FD-301 flashes to indicate an invalid setpoint.

ON/OFF SWITCHING

To turn 

OFF

 fixtures, a manually operated switch, time clock, BAS, or occupancy sensor can be installed in conjunction with the  

FD-301 and FS-PP. This instruction describes operation with an FS-series occupancy sensor and one option for using a switch. Contact 

technical support for help with other switching applications.

Operation with an Occupancy Sensor

When an occupancy sensor is installed in the FD-301 system, the fixture turns 

OFF

 if no motion is detected in the area for the length 

of time set in the sensor’s time delay, regardless of the light level. When the occupancy sensor detects motion in the area, the fixture 

initially turns 

ON

 to full output, then the FD-301 reads the illuminance level and begins automatic dimming to maintain the target 

illuminance level.

Operation with a Switch

When a switch is used to turn 

OFF

 power to the fixture and the FD-301 is wired as shown in Figure 6, the fixture and FD-301 system 

turn 

OFF

 when the switch opens. When the switch is again closed, the fixture initially turns 

ON

 to full output, then the FD-301 reads the 

illuminance level and begins automatic dimming to maintain the target illuminance level.

INSTALLATION IN THE FIXTURE

Mount the FD-301 so the fixture’s lamp output (candlepower curve profile) is outside the sensor’s peak sensitivity area.

1.  Install the FS-PP as directed in the installation instructions provided with the power pack.
2.  Determine an appropriate mounting location for the FD-301 inside the light fixture. Cut a 3/4” diameter hole through the sheet 

metal in the bottom of the fixture.
A beauty ring and thumbscrew collar are supplied to secure the FD-301 lens through the fixture wall. Depending on the wall 

thickness and curvature, you may need to use the thumbscrew collar on the inside or outside of the fixture, or not at all, as shown 

in Figure 3.

3.  Remove the beauty ring and thumbscrew collar from the FD-301 lens pipe.
4.  Insert the lens from the inside of the fixture, through the hole in the bottom of the fixture.

•  If the lens extends too far outside the fixture, use the thumbscrew collar to adjust the depth.
•  Tighten it to the outside of the fixture or tighten it against the sensor body before inserting the lens through the fixture wall.
•  Then put the beauty ring onto the lens pipe and tighten it securely.

WIRING

For daylight dimming control (see Figure 4):

1.  Plug in the RJ-45 from the FD-301 into the TO SENSOR receptacle on the FS-PP.
2.  Connect the violet and grey wires from the FD-301 to the 0-10V inputs on the dimming ballast.

To also provide 

ON/OFF

 control using an occupancy sensor, see Figure 5, or to provide manual 

OFF

 control using a local switch, see 

Figure 6. For other control options, contact technical support.

Configuring the Optional Occupancy Sensor

Use the instructions supplied with the FS-series sensor to install the sensor in the fixture, connect the sensor to the FS-PP and to set the 

time delay. Some FS-series occupancy sensors are equipped with a light level sensor. Be sure to set the light level on the occupancy 

sensor to maximum, meaning that even the brightest ambient light will not hold the lights off.

Tighten

FD-301

FS-PP

FD-301

Fixture

wall

Thumbscrew collar 

+ beauty ring

Fixture

wall

Thumbscrew collar 

+ beauty ring

Beauty ring only

Figure 3:  Installing in a light fixture

WARNING:

 ALWAYS MAKE SURE 

POWER TO THE FIXTURE IS OFF BEFORE 

WORKING WITH THE POWER PACK.