LEGRAND Wattstopper CU-250 Скачать руководство пользователя страница 3

3

INITIAL POWER-UP DELAY

There is an initial warm-up and calibration period the first time power is applied to the unit, after a power failure lasting more than 5 

minutes and after the load is replaced. However, the lights can be turned 

ON/OFF

 manually by pressing the 

ON/OFF

 button at any time 

when power is supplied to the unit.

 

SENSOR ADJUSTMENT

To adjust the CU-250, you use controls located under the 

ON/OFF

 button. The wall switch cover plate must be removed to gain access 

to the adjustment dials under the 

ON/OFF

 button.

NOTE: 

For multi-way operation, the Time Delay adjustments should be the same in all sensors related to 

the same load.

1.  Firmly grasp the side edges of the Lock Bar and gently pull it away from the switch face until it clicks. 

Do NOT attempt to pull the Lock Bar off of the switch!

2.  Firmly grasp the side edges of the 

ON/OFF

 button. Slide the button downward approximately 1/2 

inch to expose the adjustment dials.

Adjusting the Time Delay

Turn the right dial counter-clockwise to reduce the amount of time the lights will remain 

ON

 after the last 

motion detection (minimum = 15 seconds). Turn the dial clockwise to increase this time delay  

(maximum = 30 minutes).  

You can select the following values:  

15 seconds • 5 minutes • 15 minutes • 30 minutes. 

NOTE: 

Do not overturn the Time Delay adjustment dial!

Adjusting the Ultrasonic Sensitivity Level

This feature is factory set at around 70% of maximum. Turn the left dial counter-clockwise to reduce ultrasonic detection sensitivity. Turn 

the same dial clockwise to increase the ultrasonic detection sensitivity.

NOTE: 

Do not overturn the ultrasonic sensitivity adjustment dial!

c. 

Multi-way wiring using one CU-250 and up to four RH-253s:

 

One CU-250 can be connected with up to 4 RH-253 single 

pole momentary wall switches for multi-way 

Manual-ON/OFF

 

control of one single load. 

The CU-250 must be installed in 

the wiring wall box that connects to the load.

•  Connect the existing wires to the wire leads on the CU-250 

sensor as indicated below (See Fig. 3c). Cap them securely 

using wire nuts provided.

•  Connect the green or non-insulated (copper) GROUND wire 

from the circuit to the green wire on each CU-250.

•  Connect the NEUTRAL wire from the circuit and from the 

lamp (LOAD) to the white wire on the CU-250.

•  Connect the power wire from the circuit box (HOT) to the 

black wire on the CU-250 (TRAVELER 1) and to one terminal 

on each RH-253 single pole momentary switch.

•  Connect the lamp power (LOAD) to the red wire on the CU-250.
•  Connect the yellow wire on the CU-250 (TRAVELER 2) to the 

other side of each RH-253 single pole momentary wall switches.

4. 

Put the CU-250s (and RH-253s if applicable) into their respective 

wall boxes.

 

Position them with the lens positioned above the 

ON/OFF

 button (lens 

at top, 

ON/OFF

 button at bottom). Secure to the wall box with the 

screws provided.

5. 

Make any necessary adjustments.

 

See the SENSOR ADJUSTMENT section for information.

6. 

Install cover plate.

 

Install industry standard decorator wall switch cover plate  

(not included).

7. 

Restore power to the circuit.

 

Turn on the breaker or replace the fuse.

IMPORTANT: 

Wire the auxiliary unit to the same branch circuit as the 

master unit and the load. If the load cannot be controlled 

from the auxiliary unit check wiring to be sure both the units 

and the load are on the same branch circuit.

AUXILIARY CU-250

MASTER CU-250

TOP

INDOOR USE ONLY

Red

Ground

Yellow

Black

White

Red

Ground

Yellow

Black

White

Load

Traveler 1

Traveler 2

Neutral

Hot/Line

Neutral

TOP

INDOOR USE ONLY

Fig. 3b:  Reference wiring diagram, 3-way using two CU-250s

TOP

INDOOR USE ONLY

Red

Ground

Yellow

Black

White

Load

Traveler 2

Hot/Line

Neutral

Traveler 1 (Hot)

RH-253

Ground

RH-253

Ground

Ground

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Traveler 2

Traveler 1

CU-250

Fig. 3c:  Multi-way wiring using one CU-250 and three RH-253s

Fig. 5:  Sensor Adjustment Controls

TOP

INDOOR USE ON LY

Adjustment

Dials

Lock Bar

Slide Down

ON/OFF

Button

Time Delay

30 

   Min.

Sec.

15 

Min.

15

Min.

ma

x

mi

n

Sensitivity

09575r1

Min.

Se

c

15

   

Min.

Sec.