LEGRAND VANTAGE CIS10-DIN Скачать руководство пользователя страница 2

 

I N S T A L L A T I O N

 

©Vantage, 1/3/2017 / IS-0584-B 

DIN WireLink and RadioLink CIS — MODEL: CIS10-DIN & STIDER121 

page 2 of 2 

Side

Label

Enlarged

NOTE:  RadioLink Model – Top Label; Power Input Connection is 
15-36VDC or 12-28VAC, 250mA IN 

RadioLink Model FCC Information 

This device contains transmitter module: 
FCC ID:  PII-VSUB075-1 or PII-VSUB235 
IC ID: 3505A-VSUB0751 or 3505A-VSUB235 
This device complies with Part 15 of the FCC Rules. Operation is subject to 
the following two conditions:  (1) This device may not cause harmful 
interference, and (2) this device must accept any interference received, 
including interference that may cause undesired operation. 

 
Changes or modifications to this product not expressly approved by 
Vantage Controls could void the user’s authority to operate this product.

 

network.

 The Status LED will blink steadily when a station has been 

added to the network and configured. 
 
*NOTE: A new feature with Design Center 2.3 and up is the ability 
to configure RadioLink stations the same way WireLink stations are 
configured, e.g., 3-button press. When configuring stations, if the 

Exclude RadioLink Bus

 check box, under 

Settings | System 

Preferences

, is 

not

 checked, all RadioLink stations go back to non-

programmed mode when the Configure Stations button on the tool 
bar is clicked. The station’s LEDs will all blink while in configure 
station mode. After configuring stations and clicking the Configure 
Stations button again to turn configure stations mode off, all 
RadioLink stations need to log back on to the system before 
working as programmed. Allow time for this to occur. 
 
Diagnostic and Test Information 
Each contact input has an actuator button and 2 status LED's. The 
actuator button shorts the input to ground. The Contact State LED 

illuminates when the contact input is grounded. The Program State 
LED operates the same as switch LEDs on a keypad station. When 
grounded, Contact States trigger the Program State ON or OFF 
depending on whether the contact’s polarity is set to Normally 
Open or Normally Closed. 
The Status LED blinks steady on and off for 1, 2, 3 or 4 blinks 
followed by a pause.  
One Even Blink: 

CIS is operating correctly and is configured. 

Two Blinks: 

CIS is operating correctly but is not configured 
(wired model). 

Three Blinks: 

CIS is not communicating with the Main  

Controller, verify station bus wiring or if 
RadioLink it is not yet configured. 

Four Blinks: 

Factory problem. Please contact the factory. 

Five blinks: 

Configuration mode. 

 
 

 
 

 
Line Drawings 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 

Отзывы: