Circuit breaker TX
3
6000 A
up to 63 A (1 module per pole)
Cat. N° (s) : 4 033 49 to 4 035 68, 4 037 12 to 4 037 78
5. GENERAL CHARACTERISTICS
(continued):
Coordination between modular circuit-breakers and MCCBs, three-phase network (+ neutal) 400 / 415 V~ according to
IEC/EN 60947-2:
For TT or TN neutral system in 230/400 V network, to know the breaking capacity of the combination of a double pole breaker (connected between
phase and neutral under 230 V) downstream of a triple-pole circuit-breaker, take the values shown in Tables 230/400 V.
m.c.c.b. upstream
DPX 250ER
DPX
3
250 / DPX
3
250 +RCD
(Thermal-magnetic & electronic)
25 - 36 - 50kA
25 - 36 – 50 - 70kA
m.c.b. downstream
100A
160A
250A
100A
160A
200A
250A
TX
3
6000A
B, C & D Curves
<6A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
6A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
10A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
13A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
16A
25kA
25kA
25kA
25kA
25k
25kA
25kA
20A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
32A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
40A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
50A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
63A
20kA
20kA
20kA
25kA
25kA
25kA
25kA
m.c.c.b. upstream
DPX / H / L 250
(Thermal-magnetic & electronic)
DPX / H / L 630
(Thermal-magnetic & electronic)
36 – 70 – 100kA
36 – 70 – 100kA
m.c.b. downstream
25A
40A
63A
100A
160A
250A
250A
320A
400A
500A
630A
TX
3
6000A
B, C & D Curves
<6A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
6A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
10A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
13A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
16A
25kA
25kA
25kA
25kA
25k
25kA
25kA
25kA
25kA
25kA
25kA
20A
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25A
-
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
32A
-
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
25kA
40A
-
-
25kA
25kA
25kA
25kA
20kA
20kA
20kA
20kA
20kA
50A
-
-
25kA
25kA
25kA
25kA
16kA
16kA
16kA
16kA
16kA
63A
-
-
-
25kA
25kA
25kA
16kA
16kA
16kA
16kA
16kA
According to the curves and ratings of circuit breakers, attention to the magnetic (or electronic) threshold and to the size of upstream circuit breakers which must
necessarily be higher.
Technical data sheet: F01547EN/01
Updated: 15/10/2014