38
6.5
Start-up procedure
1. Insert the battery fuses into the appropriate fuse breakers of the Trimod HE UPS if the model includes them and inside
the external Trimod HE BATTERY cabinets (if present).
2. Close the battery fuse breakers of the UPS and Trimod HE BATTERY FB+ and FB- (if present).
INDICATION
Before turning on the UPS it is necessary to select the correct output configuration (Single phase/ Three Phases 120° /
Three independent phases). In order to do so, the rest of the procedure must be applied.
3. With the UPS off, press the ENTER key on the control panel and keep it held down until the text "Language" appears.
Using the ARROW UP and ARROW DOWN keys, select the required language and confirm the choice with the ENTER
key.
4. Press the ESC key to leave the Language page. The text "Service Mode" appears on the display.
For further information about the function Service Mode and how the control panel works, consult the user manual.
CAUTION
Trimod HE is able to recognise the presence of non aligned firmware among the power modules and therefore prevent
the start-up.
In Service Mode the status indicator flashes orange rapidly and the texts "Service Mode" and "PM FW not updated!"
alternate.
Follow the path Power Modules
PM SW update to update the power module firmware. It is possible to choose
Update all PM to check and if necessary update all the power modules, while with the option Single PM SW update you
can select the specific power module to update.
5. Press the ENTER key to enter the menu. Using the ARROW UP and ARROW DOWN keys, it is possible to move the
selection on the display; the ENTER key is used to confirm the choice and the ESC key is used to cancel the choice.
Follow the path UPS Setup
Output
Inverter
Select “Three Phases 120°” / “Three Phases indep.” / “Single Phase” in accordance with the type of load and distribution
downstream of the UPS.
CAUTION
The inverter output configuration must correspond with the configuration set on the output terminal strip during
the installation.
Wrong connections or incorrect output configurations may cause injury and/or damage.
Trimod HE 10
Trimod HE 15-20
Trimod HE 30 TM
Trimod HE 30 TT
Trimod HE 40-60
6. Configuration and Start-up
Содержание Trimod HE 10
Страница 1: ...Trimod HE Installation and maintenance manual Item LE10273AA 03 18 01 CT ...
Страница 2: ...2 EN ENGLISH 3 Trimod HE ...
Страница 15: ...Trimod HE Installation and maintenance manual 15 Trimod HE 30 TT Trimod HE 30 TM ...
Страница 16: ...16 3 Models Trimod HE 40 Trimod HE 60 ...
Страница 57: ...Trimod HE Installation and maintenance manual 57 Notes ...
Страница 58: ...58 Notes ...
Страница 59: ...Trimod HE Installation and maintenance manual 59 ...