Step 4: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note:
The battery charges fully during the first five hours of normal operation. Do not expect full battery run
capability during this initial charge period.
Step 5: Install software
tshutdown. You may insert the CD provided into the CD-ROM to install the monitoring software.
If not, please follow the on screen instructions to install the software. When your computer restarts, the
monitoring software will appear as an orange plug icon located in the system tray near the clock.
Step 6: External battery connection
This UPS series is not including batteries. Batteries are connected in a separate cabinet with protection.Please
connect external batteries as below chart.
Button
Function
•
Turn on the UPS:
Press and hold ON/Mute button for at least 2 seconds to
turn on the UPS.
•
Mute the alarm:
When the UPS is on battery mode, press and hold this
button for at least 5 seconds to disable or enable the alarm system.
But it is not applied to the situations when warnings or errors occur.
ON/Mute button
•
Up key:
Press this button to display previous selection in UPS setting mode.
Switch to UPS
self-test mode: Press and hold ON/Mute button for
5 seconds to enter UPS self-testing while in AC mode, ECO mode,
or Converter mode.
•
Turn off the UPS:
Press and hold this button at least 2 seconds to turn off
UPS. UPS will be in standby mode under power normal or transfer to Bypass
mode if the Bypass setting is enabled by pressing
OFF/Enter button
this button.
•
Confirm selection key:
Press this button to confirm selection in
UPS setting mode.
•
Switch LCD message:
Press this button to change the LCD message for
input voltage, input frequency, battery voltage, output voltage and output
frequency. It will return back to default display when pausing
for 10 seconds.
Select button
•
Setting mode:
Press and hold this button for 5 seconds to enter UPS
setting mode when UPS is in standby mode or Bypass mode.
•
Down key:
Press this button to display next selection in
UPS setting mod
•
Switch to Bypass mode:
When the main power is normal, press ON/Mute
ON/Mute + Select
and Select buttons simultaneously for 5 seconds. Then UPS will enter to
button
Bypass mode. This action will be ineffective when the input voltage is out of
acceptable range.
TO EXTERNAL BATTERY
+
-
7
Recommended External Breaker Rating
S. No.
Rating of UPS
Battery Breaker
1
1 kVA - FM/FMI
50 A DC (C Curve)
2
2 kVA - FM/FMI
50 A DC (C Curve)
3
3 kVA - FM/FMI
50 A DC (C Curve)
8
5. OPERATIONS
5-1. Button operation