INSTALLATION INSTRUCTIONS

F-2935

INSTALLATION (cont’d)

CAUTION: LED Lamps operate at 4VDC ONLY. Fixture
is intended to be powered by external low voltage
regulated power supply. To avoid electrical overload,
use only with Kenall Millenium Metrex series unit
equipment or master exit signs equipped with
remote exit sign power capability.

•   Directional Indicators (Fig. 4): Configure 

DIRECTIONAL ARROWs as needed. To remove 

DIRECTIONALARROW COVER, use 7/16” nut 

driver (not supplied) to loosen RETAINER NUT 

approx. one complete turn. Push in cover from 

outside. Tighten RETAINER NUT to secure COLOR 

FILTER PANEL and aluminum LIGHT MASK (if 

provided).

   Minimum 12” supply wire pigtails must 

extend from electrical junction box for field 

connections within fixture enclosure.

Installation
•    Disassembly (Fig.1): Remove SHIELD by

       loosening (4) CAPTIVE SCREWS at 

       corners Remove STENCIL PANEL.
•   Mounting Place HOUSING over an installed 

electrica junction box (drill points provided 

for temporary j-box attachment prior to 

permanent mounting). Locate and drill 4 

pilot holes in mounting surface using 

HOUSING as a template. (Fig.2): For wet 

location installation, attach self-adhesive 

pad GASKETS to HOUSING at (4) mounting 

holes and center wiring hole. Observe correct 

orientation of UP indicators molded into 

housing. Using ¼” fasteners and anchors 

appropriate for the mounting surface (not 

supplied), attach HOUSING to structure.

•   Wiring (Fig. 3): Route 12” supply wire pigtails 

through WIRING ACCESS HOLE. Secure supply 

wires with CABLE TIE provided. Connect 

supply wires to appropriate terminals in 

TERMINAL BLOCK. Lead color coding: Gray= 

Negative, Brown=Positive.