2
The product is designed to be mounted directly to a luminaire, either on the inside or outside, or flush into the ceiling.
The detector should be sited so that the occupants of the room fall inside the detection pattern (shown opposite), at a
recommended ceiling height of 2.8m. Note that the lower the sensor is installed the smaller the detection range will be,
subject to the parameters shown on the detection diagram.
•
For optimum operation of the lux sensor, the lens must shielded as much as possible from the light source.
•
If flush mounting in a panel >6mm thick, remove bottom of retention arms with side cutters.
•
Avoid direct sunlight entering the sensor.
•
Do not site within 1m of forced air heating or ventilation.
•
Do not fix to a vibrating surface.
Installation
Detection diagram
Range
Walk towards
Walk across
Height
Range Diameter
7m
10m
2.8m
5m
Height
Range Diameter
7m
16m
2.8m
9m
Note: illustration shows an average of the walk across
Flush mounting
Side mounting
The product can be mounted
using the flush mount ring as
shown. If flush mounting in a
material that is greater than 6mm
thick, remove bottom of retention
arms with side cutters. A 32mm
diameter hole will be required to
mount the flush mount ring.
Ø19.5m
Ø3.5m
19mm
Use the lugs on rear of detector to
secure into thin sheet metal (1mm
max.).
Surface mounting