![LEGRAND 5 551 01 Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/legrand/5-551-01/5-551-01_technical-data-manual_1870380009.webp)
9/10
Technical data sheet: F01811EN/02
Updated: 27/11/2015
Created: 08/10/2013
Plugs, mobile sockets,
panel mounting sockets,
surface mounting sockets,
P17 Tempra Pro IP44 and low voltage 66/67
Catalogue number(s): 5 551 01/02/04/05/06/07/08/09/10/12/13/21/
22/24/25/ 26/27/28/29/30/32/33/51/52/54/55/
56/57/58/59/60/62/63/81/84/85/86/88/89/90/
92/93 - 5 552 11/14/15/16/17/18/19/20/22/23/
31/34/35/36/37/38/39/40/42/43/51/54/55/56/
57/58/59/60/62/63/81/84/85/86/88/89/90/92/
93 - 5 553 01/04/05/06/08/09/12/21/24/25/26/
28/29/32/51/54/55/56/58/59/62/81/84/85/86/
88/89/92 - 5 554 14/15/16/18/19/21/22/31/34/
35/36/38/39/41/42/43/51/54/55/56/58/59/62/
63/81/84/85/86/88/89/91/92
6. INSTALLATION (CONTINUED)
6. INSTALLATION (CONTINUED)
7. CONNECTION
8
- CABLE ENTRY POINTS
4 threaded and sealed cable entries at the top and the bottom and
marking at the back of the box for ISO cable glands or trunking.
- POSITION MARKS
Information engraved on the ring cover of IP66/67 products means
the user can quickly check whether it is in the open or closed position.
Marking area on the socket flap cover or on the plug skirt for easy
identification by the user.
- Marking/identification area
9
- OPENING LEVER
For easier connections/disconnections. Cover held open on panel
sockets and surface mounting sockets.
7.1 Connection capacity
Connection cross-section for pilot wire
Type
Intensity
Size of
conductors
(mm ≤)
Size of
conductors
Surface mounting
socket and panel
mounting socket
16A
1.5 to 4
Rigid
16A
1 to 2.5
Rigid
Mobile plugs and
sockets
32A
2.5 to 6
Flexible
32A
2.5 to 10
Flexible
7.2 Tightening torque of connection terminal screws
- 16A LV: 0.8 to 1.2 Nm
- 32A LV: 1.2 to 1.5 Nm