PRO1 Sentry Switched DC PDU
170 of 211
set line
Sets line configuration values.
Command Syntax
set line email [disabled | enabled] <name | id | ALL>
set line load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set line load hyst <value>
set line snmpt [disabled | enabled] <name | id | ALL>
Parameters
The
set line
command uses the following parameters:
Email notification for line events.
Hyst
Hysteresis between event state and recovery.
Load
Current load for a line. min = 0A, max (current limit) in
show lines
command,
hyst 0.0-10.0A (default 1.0A).
SNMPT
SNMP trap notifications for line events.
Sub-Parameters
The
set line
command uses the following sub-parameters:
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Command Access
Admin level only
Содержание 48DCWC-04-2X100-D0NB
Страница 1: ......
Страница 2: ...Sentry Switched DC PDU 2 of 211...
Страница 10: ...Sentry Switched DC PDU 10 of 211 Mounting Bracket The 48DCWC 16 2X100 A0 mounting bracket...
Страница 12: ...Sentry Switched DC PDU 12 of 211 Mounting Bracket The 48DCWC 04 2X100 D0NB mounting bracket...
Страница 14: ...Sentry Switched DC PDU 14 of 211 Mounting Bracket The 48DCWC 12 2X100 A1NB mounting bracket...
Страница 16: ...Sentry Switched DC PDU 16 of 211 Mounting Bracket The 48DCWC 08 2X100 B0NB mounting bracket...
Страница 18: ...Sentry Switched DC PDU 18 of 211 Mounting Bracket The 48DCWC 04 4X070 D0NB mounting bracket...
Страница 20: ...Sentry Switched DC PDU 20 of 211 Mounting Bracket The 48DCWC 04 4X125 E0NB mounting bracket...
Страница 22: ...Sentry Switched DC PDU 22 of 211 Mounting Bracket The 48DCWC 10 2X300 E0NB mounting bracket...