23
Option of changing the operating mode by entering a code.
A parameter setting is changed by entering the following on the controller keypad:
• 1 - Enter the code
• 2 - E (validation)
- C: permet d’annuler une saisie en cours.
Code
Control
9030
switch to night mode (intruder)*
9031
switch to day mode (surveillance)*
9039
switch to parameter setting mode: This code is only taken into account if the locking configuration
(ST8) is at position "1-2" (factory position 2-3) .
9090
parameter loading by default: Deletion of all current parameter settings and return to default
parameter settings. The code 9090 must be entered twice in order to prevent incorrect operation.
Example: 9090 e 9090 e
9098
listing of the system parameter settings: Transmission of the entire settings to the controller
system link.
0000
Controller reset: Resets the controller in the same way as a return of power. The code 9999 must be
set in the parameters in order for this to be taken into account.
Example: 0000 e 9999 e
*When operating mode selection via the keypad is activated each changeover from one mode to another is
memorised. If the power supply is cut, the controller starts up in the last mode that was activated.
the controller starts up in surveillance mode for the initial commissioning.