Niky S 1-1.5-2-3 kVA 

15

•  Take your UPS out of its packing.
•  Make sure the mains supply voltage is identical to the one indicated in the label placed on the rear 

of the UPS.

•  Switch the UPS on by pressing the ON/OF button until the buzzer emits a sound and check it 

operates correctly with the mains  (green LED on), and the display is on without alarm notifications.

•  Switch the UPS off by pressing the ON/OFF button for at least 3 seconds until the LED and the 

display shut down.

•  After switching off the UPS, connect the load power cable to the UPS output using the outlets 

located on the back of the UPS.

•  Switch on your UPS and then the load to check it operates correctly with the mains (green LED on).
•  Keep the UPS on for 8 hours to recharge battery before using it. UPS can also be used before battery 

is completely charged, but in this case back up time available during black out will be shorter.

Light signals:

The color of the LEDs on the front panel has the following meanings :
•  Fixed green LED: mains present and regular, batteries recharging
•  Green LED flashing every 3 sec: running on battery
•  Green LED flashing every 0.5 sec: autonomy in reserve
•  Green/red LEDs flashing: test or restart after end of autonomy
•  Fixed red LED: failure or battery overload

Acoustic signals:

•  Intermittent sound every 3 sec: running on battery
•  Intermittent sound every 0.5 sec: autonomy in reserve
•  Continuous sound: failure, overload or batteries flat

3 Installation

4 Signals and controls

CAUTION 

While wiring the outlet line, make sure the total length of the cable, from the UPS to the 

farthest utility, does not exceed 10 metres.

NOTICE 

Never disconnect the 230 V power plug while the UPS is operating since this would 

disconnect the earthing protection both from the UPS and from the loads connected to it.

EN

Содержание 310006

Страница 1: ... S 1 1 5 2 3 kVA Index 1 Introduction 14 2 Conditions of use 14 3 Installation 15 4 Signals and controls 15 5 Overload and automatic shutdown 16 6 Features 16 7 Changing batteries 18 8 Possible malfunctioning 19 9 Technical features 20 ...

Страница 2: ...ains plug is disconnected there are no parts inside that the user can repair The UPS Niky S has been designed to work in closed clean rooms where there are no inflamma ble liquids or corrosive substances and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equi pments that are sensible to electro magnetic fields engines floppy disks spe...

Страница 3: ... is completely charged but in this case back up time available during black out will be shorter Light signals The color of the LEDs on the front panel has the following meanings Fixed green LED mains present and regular batteries recharging Green LED flashing every 3 sec running on battery Green LED flashing every 0 5 sec autonomy in reserve Green red LEDs flashing test or restart after end of aut...

Страница 4: ...e mains on press the ON button for at least 3 seconds to perform the battery test if the batteries are working correctly the UPS will switch to battery operation for 10 seconds and then return to mains operation In case of batteries below the minimum charge level the battery LED will flash for 5 seconds if there are exhausted batteries or batteries needing replacing the battery LED will stay on Bu...

Страница 5: ... Software connection Niky S 1 1 5 2 3 kVA The UPS is equipped with a USB and an RS232 interface thanks to which it is possible by means of a computer to access a set of data regarding the operation of the UPS and control the operating system unattended shutdown Software is available as on option for Win98 ME 2000 Novell and Linux from the website www ups legrand com without charge User license is ...

Страница 6: ...ruptible power supply 2 Unplug the power cable from the mains socket 3 Change the batteries with others of the same type and make or having the same features Keep clear from fire to avoid explosion while handling batteries Do not open or tamper with the battery case because it contains toxic electrolyte that could be harmful for your skin or eyes Keep out of children s reach NOTICE The batteries m...

Страница 7: ...tery mode it shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninte...

Страница 8: ...ing Degree of protection as per IEC529 IP20 Noise level at 1 meter 40 dBA Electrical input specifications Rated input voltage 230 V Range of input voltage from 160 V to 290 V Rated input frequency 50 60 Hz 3Hz Maximum input current 4 Arms 6 Arms 8 Arms 12 Arms Number of input phases Single phase Waveform on output With battery operation sinusoidal Type of operation line interactive Electrical spec...

Страница 9: ... load 5 min 5 min Charging time 4 hours at 90 of the charge Technical data and number of batteries n 2 mainte nance free sealed lead bat tery 12V 7 2 Ah n 2 mainte nance free sealed lead battery 12V 9 Ah n 2 mainte nance free sealed lead acid battery 12V 7 2 Ah n 2 mainte nance free sealed lead acid battery 12V 9 Ah Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 S...

Страница 10: ...rew 8 Batteries exhausted notification 9 Bypass notification 10 Mains voltage low notification 11 Mains voltage too high notification 12 UPS output present notification 13 Wrong ground connection notification 14 Overload notification 15 Battery charge percentage notification 16 Battery charge selection button notification 17 RJ45 Port 18 DIP Switch 19 USB interface socket 20 RS232 serial interface...

Отзывы: