background image

87045 LIMOGES Cedex

Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88

Technical data sheet: F00983EN/00

Catalogue number(s):  026 21

Updated on: 

Created on: 20/12/2010

1/3

Controller - 1 x 1000 W output with 

dimming - All loads

CONTENTS

1. USE

This device is a power unit used for managing lighting loads.
The load(s) can be controlled locally either manually or by SCS 
commands associated with it (them). They can also be controlled 
automatically by digital detectors.
The use of SCS commands and digital detectors requires an SCS 
power supply and an addressing module* to be wired on the 

 BUS.

*  The addressing module is not necessary if the installation is 

equipped with the software packs.

2. TEChNiCAl fEATUrES

CONTENTS                            

  Page

1.   Use . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
2. Technical features  . . . . . . . . . . . . . . . .1
3. Overall dimensions. . . . . . . . . . . . . . . .2
4. Connection . . . . . . . . . . . . . . . . . . . . . .2
5.  Parameter setting . . . . . . . . . . . . . . . . .3
6. Operation . . . . . . . . . . . . . . . . . . . . . . .3
7. Maintenance. . . . . . . . . . . . . . . . . . . . .3
8. Standards . . . . . . . . . . . . . . . . . . . . . . .3

230 V~

1000 W

4.3 A

1000 W

4.3 A

1000 VA

4.3 A

1000 VA

4.3 A

110 V~

500 W

500 W

500 VA

500 VA

1

2

3

4

1

 

Incandescent bulbs

2

 

Tungsten halogen bulbs

3

  

Tungsten halogen bulbs with ferromagnetic transformer

4

  

Tungsten halogen bulbs with separate electronic transformer

Number of supply terminal blocks

1

Number of load terminal blocks

1

Connection terminals

Terminal types

screw

Terminal capacity

2 x 2.5 mm

2

Number of RJ 45

1

Mains voltage

100-240 V~

Frequency

50/60 Hz

Location category

Internal

Degree of protection

Penetration by solid  
and liquid matter

IP20  
(installation in an enclosure)

Impact resistance

IK04

Number of modules

6

Usage temperature

-5°C to +45°C

Storage temperature

-20°C to +70°C

No load power consumption

0.3 W

Weight

327 g

2. TEChNiCAl fEATUrES (continued)

LEARN indicator: 
indicates the teach 
phase or RESET

Indicator  
(on if output 
activated)

Configurator

Control 
button

LEARN button

SCS BUS connection  
(RJ 45)

CAUTiON:

  

Do not combine on 

the same channel

3

+

4

Only one transformer for use with an electronic switch must be used.