SOMMAIRE
Technical data sheet: F01163EN/01
Updated: 30/03/2015
Created: 07/07/2010
Catalogue number(s): 0 882 30
Configuration tool with screen
2
Select the application
Alert window warning that some data may be lost. Select Continue to
start updating.
3
Eg: Lighting management
Updating is complete.
4
Connect the configuration tool to the PC
Once connected, the configuration tool should switch on. If not,
disconnect and then reconnect it to the USB cable.
5
Choose whether or not to start updating
4. UPDATING (CONTINUED)
4. UPDATING (CONTINUED)
Important: The configuration tool must be switched off
Note: All technical information is available on
Commercial premises - office buildings:
Passage areas and corridors: 100 lux
Stairs: 150 lux
Canteens: 200 lux
First-aid room: 500 lux
Warehouse: 100 lux
Offices: 300 - 500 lux
Conference rooms: 500 lux
Reception rooms: 300 lux
Technical drawing: 750 lux
Manufacturing areas:
Packaging rooms: 300 lux
Visual work during manufacturing: 1000 lux
Assembly line: 1500 lux
Warehouses:
Sales areas: 300 lux
Checkout areas: 500 lux
Other examples:
Moonlit night: 0.5 lux
Well-lit street at night: 20 - 70 lux
Living premises: 100 - 200 lux
Well-lit apartment: 200 - 400 lux
Work premises: 200 - 3000 lux
Stadium at night: 1500 lux
Outside with cloudy sky: 25,000 lux
Outside in full sunshine: 50,000 to 100,000 lux
5. STANDARD EN12464-1 RECOMMENDATIONS