LEGRAND 0 035 46 Скачать руководство пользователя страница 4

4/5

Technical data sheet: S000113311EN-1 

Updated: 

Created: 13/01/2021

Cat. No(s): 0 035 46

KNX line coupler DIN

   5 .  OPERATION (continued)

5 .7 Line Coupler as TP Coupler

When Line Coupler receives telegrams (for example during 

commissioning) that use Physical Addresses as destination addresses, 

it compares the Physical Addresses of the receiver with its own physical 

address and decides on that whether it has to route the telegrams or 

not.
When Line Coupler receives telegrams that use group addresses as 

destination addresses, it reacts in accordance with the parameter 

settings. During normal operation (with Group Telegram routing set to 

filter), Line Coupler only routes telegrams whose group addresses are 

entered in its filter table.
If a telegram is routed by Line Coupler without receiving the 

corresponding acknowledgement, i.e. due to a missing receiver or to 

a transmission error, the telegram will be repeated up to three times 

(depending on the ETS setting). With the parameters "Repetitions 

if errors...", this function can be configured separately for each line 

and both kinds of telegrams. It is recommended to use the default 

parameter setting.
If not already configured as “Line Coupler”, the ETS application 

program "TP Coupler" has to be downloaded to the device. Under 

the Information tab the configuration setting can be changed by the 

drop-down menu “Change Application Program”. After changing the 

configuration setting the filter table entries can be added manually. 

Updating the application program version can also be done here.

5 .8 Line Coupler as TP Repeater

Any received telegram is routed to all lines irrespective of in which line 

it is processed. Line repeaters make no use of a filter table. It is therefore 

not important whether the telegram is generated within a line or 

whether it is sent from an upper line to a lower line via a coupler.
If a telegram is routed by Line Coupler without receiving the 

corresponding acknowledgement, i.e. due to a missing receiver or to 

a transmission error, the telegram will be repeated up to three times 

(depending on the ETS setting). With the parameters "Repetitions 

if errors...", this function can be configured separately for each line 

and both kinds of telegrams. It is recommended to use the default 

parameter setting.
If not already configured as Line/Area/BB Repeater, the ETS application 

program "TP repeater" has to be downloaded to the device. Under 

the Information tab the configuration setting can be changed by the 

drop-down menu “Change Application Program”. After changing the 

configuration setting the filter table entries can be added manually. 

Updating the application program version can also be done here.

5 .9 Default Factory Settings

Marking/Design

Line Coupler

Physical address

15.15.0

Main Line

Group telegrams 0-13

Filter (filter table is empty)

Group telegrams 14-31

route all

Physical telegrams

filter

Physical: Repetition if errors on main line

up to 3 repetitions

Group: Repetition if errors on main line

up to 3 repetitions

Telegram confirmations on main line

if routed

Send confirmation on own telegrams

no

Subline

Group telegrams 0-13

Filter (filter table is empty)

Group telegrams 14-31

route all

Physical telegrams

filter

Physical: Repetition if errors on subline

up to 3 repetitions

Group: Repetition if errors on subline

up to 3 repetitions

Telegram confirmations on subline

if routed

Send confirmation on own telegrams

no

Configuration from subline

allow

  6 . STANDARDS 

• Type of protection: EN 60 529

• Safety class III: IEC 61140

• Overvoltage class III: IEC 60664

• Degree of Pollution: IEC 60664

• Installation: EN 60 715 TH 35-75

• CE: in accordance with the EMC guideline and low voltage directives

  7 . COMMUNICATION OBJECTS

7 .1 ETS Parameters
7 .1 .1 General

ETS-Text

Range

[Default value]

Comment

Manual Function

disabled

pass all telegrams

pass all Physical 

telegrams

pass all Group 

telegrams

[pass all telegrams]

Configuration setting for telegram 

routing when the Manual Function 

is active.

Switch-off time for Manual 

Function

10 min, 1 hour,  

4 hours, 8 hours

[1 hour]

After expiry of this time period the 

Manual Function is switched off 

automatically.

Table 1: Parameter General

7 .1 .2 Main Line

For Group Telegrams and Physical Telegrams the setting “transmit all” 

is intended only for testing purposes. Please do not use for normal 

operation.

Note:

If the parameter "Send confirmation on own telegrams" is set to 

"yes", the Line Coupler systematically sends an ACK on any own 

routed telegram. Since the repeater does not use a filter table, it is 

useful to have an ACK sent along with routed telegrams.

ETS-Text

Range

[Default value]

Comment

Telegram routing

Group and Physical: 

route

configure

[Group and Physical: 

route]

route: all telegrams are routed

configure:  the following parameters 

must be set manually.

Physical telegrams

transmit all

block

[transmit all]

Physical telegrams are all routed.

Physical telegrams are all blocked.

Physical telegrams: 

Repetition

if errors on main line

no

up to 3 repetitions

only one repetition

[only one repetition]

After main line transmission error 

(e.g. due to missing receiver) 

Physical telegrams

• are not repeated.

• are repeated max. 3 times.

• are repeated once.

Group telegrams:  

Repetition

if errors on main line

no

up to 3 repetitions

only one repetition

[only one repetition]

After main line transmission error 

(e.g. due to missing receiver) Group 

telegrams

• are not repeated.

• are repeated max. 3 times. 

• are repeated once.

Telegram confirmation on 

main line

If routed always 

[always]

•  Routed telegrams to the subline 

are confirmed by an ACK on the 

main line.

•  Each telegram on the mainline is 

confirmed by an ACK.

Send confirmation on own 

telegrams

yes

no

[yes]

•  Telegrams sent out to the mainline 

are confirmed by added ACK.

• No ACK confirmation.

Table 2: Main Line Tab Parameter Settings

CONTENTS