Operation
Dynamic braking
Dynamic braking may be used to rapidly stop a motor
(Figure 9). For the RUN/BRAKE switch, use a double pole,
double throw switch rated for at least the maximum DC armature
voltage and maximum braking current.
Inhibit switch
An inhibit switch allows the motor to decelerate to zero speed
when the switch is closed. Connect a single pole, single throw
switch between H1 and H2 (see Figure 8). Close the switch to
decelerate the motor to zero speed. Open the switch to accelerate
the motor to set speed. An open-collector output rated for at least
10 mA (I
CE
) may also be used as an inhibit switch. Wire the
collector to H1, and the emitter to H2.
Figure 8. Inhibit Switch