CTR310 - INSTRUCTIONS
(
V1.0 28-09-2020
)
Electronic board controlling a 230 Vac single-phase asynchronous motor destined to sliding gate automation.
Definitions
Start (START) - Contact N.O.
Input to be used to require the opening or closing of the gate.
Pedestrian start (only by remote control)
Input to be used to require the partial opening of the gate.
Pedestrian start
control is not influent during a Start cycle until the closing step end
(closed gate). During a Pedestrian start cycle,
Start
control
is always working.
Stop (STOP) - Contact N.C.
It prevents the start of working cycle. If the
Stop
command
is supplied during the motion, it provokes the immediate stop of the gate. The gate
remain in stop as long as the contact is opened. After a
Stop
command
the following
Start
command
always starts an opening cycle. A
Stop
command supplied during the
pause time
interrupts the work cycle.
Photocell (FOT) - Contact N.C.
It is an optical barrier intended to intercept and signal the passage of people or vehicles along the path crossing the gate or in the area nearby it.
The
photocell
is affecting but during closing step and in the
pause time
. If an obstacle darkens the
photocell
while closing it provokes the stop and
motion reverse after
1,5 sec.
. The intervention of the
photocell
during the
pause time
reloads it extending the period before automatic closing.
Photostop (FS) - Contact N.C.
It is an optical barrier intended to intercept and signal the passage of people or vehicles along the path crossing the gate or in the area nearby it.
If an obstacle darkens the
Photostop
during the motion or in the step previous to the work cycle start, it determines a temporary stop of the gate.
The
blinker
signals by a fixed light the anomalous condition. As soon as the obstacle is removed an opening cycle starts, except when the gate is
fully opened. In that case a closing cycle will start. The intervention of the
Photostop
during the
pause time
reloads it extending the period before
automatic closing.
Opening stroke end (FA)
Input
N.C.
to which to connect a device signalling when the gate has completed the opening stroke.
Closing stroke end (FC)
Input
N.C.
to which to connect a device signalling when the gate has completed the closing stroke.
Safety rib (COSTA)
Input to which to connect a device that, in case of impact against an obstacle, causes the gate stop and, after a
1,5 sec
., gate reverse for
2 sec
. It is
possible to connect resistive-type safety rib (
8K2
) or with electric contact
N.C.
. Automatically the card detects the type of connected safety rib.
When you wish to change safety rib type, you should take off power supply mains from the card and then give it again after the replacement.
An obstacle pressing the safety rib in the step previous to work cycle start causes a temporary stop of the gate. The blinker signals with fixed light
anomalous condition. As soon as the obstacle is removed work cycle starts.
Blinker (LAMP)
Card gives a command
on/off
(blink) to a lamp intended to signal danger situation caused by moving gate. Blinking logics are the following ones:
Fast blinking
(2 blinks/sec.): signals
opening
step
.
Slow blinking
(1 blink/sec.): signals
closing
step
.
Fixed light
: signals that the gate is stopped waiting the obstacle obscuring the photocell, photostop or the safety rib is removed.
Fast flash
(2 flashes/sec.): signals the lack of connections on
safety rib
input
.
Motor (MOT)
Outputs for the
open / close
command of the motor connected to the gate.
Courtesy light (CORT)
Continuous control for the lamp which lights the area around the gate. The lamp is lit for approx.
2 minutes
after the cycle has ended.
Electric lock (SERR)
Impulse control for the electric lock release.
Signalling Leds
DL1 - Programming Led (red)
: It switches
on
in programming step and during gate motion.
DL2 - Stop Led (red)
: It switches
off
at a stop command in terminal board.
DL3 - Opening stroke end Led (yellow)
: It switches
off
when the opening limit switch is activated.
DL4 - Closing stroke end Led (yellow)
: It switches
off
when the closing limit switch is activated.
DL5 - Photostop Led (yellow)
: It switches
off
when photoelectric cell is obscured.
DL6 - Photocell Led (yellow)
: It switches
off
when the photocell is obscured.
DL7 - Start Led (green)
: It switches
on
at a start command in terminal board.
Trimmer (RV1)
It regulates torque of the electric motor. Clockwise rotation increases the thrust of the gate. During the
soft stop
step, the regulation is disabled.
Programming keys
P1 -
Allows to insert/cancel the remote control codes in the memory
P2 -
Allows to set the pause time
P3 -
Allows to set the working time of the gate
Dip-switches
DP1 - Automatic closing
(
ON =
Step-by-step with automatic closing
OFF =
Step-by-step without automatic closing).
DP2 must be ON.
DP2 - Condominium logic
(
ON =
Step-by-step
OFF =
Condominium mode)
DP3 - Immediate closing
(
ON =
Step-by-step with immediate closing
OFF =
Step-by-step without immediate closing).
DP2 must be ON.
Technical features
Slow-down (soft stop)
At stroke end the unit reduces the speed of the gate (
Soft stop
function) so to avoid strong impacts.
Radio receiver
The electronic card
CTR310
contains a 3 channels radio receiver. The receiver can memorize up to
100
codes. The channel 1 of receiver acts as
Start
, while the channel 2 acts as
Pedestrian Start
. The channel 3 switches on the
Courtesy light
for approx.
2 minutes
.
Electric power lack
Following to a temporary electric power lack, at recovery the first
Start
control determines an opening cycle.
Opening with Timer
If the gate opening is controlled by a Timer, it is necessary to enable Condominium working logic.