                                            EM542S Digital Stepper Drive User Manual              

Page | 3   

 

2.4 Elimination of Heat   

 

EM542S’s working temperature is less than 60

Ԩ

 (140°F) 

 

It is recommended to use automatic idle-current mode to reduce motor heating. That means set the SW4 pin of 
DIP switch at “OFF” position. 

 

It is recommended to mount the drive vertically to maximize heat sink area. Use forced cooling method to cool if 
necessary. 

3. Connection Pin Assignments and LED Indication 

 

Figure 2

  Connectors, DIP switches, and LED locations 

The EM542S has four terminal block connectors P1, P2, P3 & P4 (see above picture), and two DIP switch selectors S1 
& S2. P1 is for control signal connections, P2 is for fault output, P3 is for power connection, and P4 is for motor 
connection. 

3.1 P1 - Control Connector Configurations 

PIN 

Details 

PUL+ 

Pulse Connection: Required. 

(1)

 5-24V, optically isolated, differential. 

(2) 

Maximum 200 KHz 

input frequency. 

(3)

 Pulse width of 2.5

μ

s or longer.

 (4)

 In single pulse (step & direction) control 

mode, this input signal represents a pulse which is active at the rising or falling voltage edge (set 
by DIP switch SW13); in double pulse (CW/CCW) control mode, this input signal represents 
clockwise (CW) pulse which is active at both high voltage level and low voltage level. 

PUL- 

DIR+ 

Direction Connection: Required. 

(1) 

5-24V, optically isolated, differential. 

(2) 

Maximum 200 

KHz input frequency. 

(3)

 Pulse width of 2.5

μ

s or longer.

 (4) 

Minimal DIR signal setup time 

should be at least 5

μ

s.

 (5)

 In single pulse (step & direction) control mode, this signal represents 

controls motion rotation direction; in double pulse (CW/CCW) control mode, this input signal 
controls counterclockwise (CCW) rotation direction and is active at both voltage high level and 
low level. 

DIR- 

ENA+ 

Enable Connection: Optional. 

(1) 

Optically isolated, differential.

 (2)

 Disable the drive by 5-24V 

input connection; enable the drive by 0-0.5 VDC connection. 

(3)

 This connection is optional 

(defaulted to unconnected) with drive enabled. 

(4)

 By default, motor shaft is unlocked when drive 

disabled but can be configured to shaft locked by DIP switch SW15. 

ENA- 

Содержание EM542S

Страница 1: ...EM542S Digital Stepper Drive User Manual User Manual EM542S Digital Stepper Drive Revision 1 0 2017 All Rights Reserved ...

Страница 2: ...g or otherwise without approval from Leadshine While every precaution has been taken in the preparation of the book Leadshine assumes no responsibility for errors or omissions Neither is any liability assumed for damages resulting from the use of the information contained herein This document is proprietary information of Leadshine that is furnished for customer use ONLY Information in this docume...

Страница 3: ...Motor Connection 5 5 2 6 lead Motor Connection 6 5 3 8 lead Motor Connection 6 5 3 1 Series Connection 6 5 3 2 Parallel Connection 6 6 Power Supply Selection 7 6 1 Regulated or Unregulated Power Supply 7 6 2 Power Supply Sharing 7 6 3 Selecting Supply Voltage 7 7 DIP Switch Configurations 7 7 1 Output Current Configuration SW1 3 8 7 2 Idle Current Configuration SW4 8 7 3 Micro Step Configuration S...

Страница 4: ...EM542S Digital Stepper Drive User Manual 11 Protection Functions 12 12 Troubleshooting 13 13 Warranty 14 14 Contact Us 15 ...

Страница 5: ...MA 17 23 and 24 stepper motors 1 1 Features Step direction PUL DIR or CW CCW double pulse control 20 50VDC supply voltage 200 KHz max pulse input frequency 16 micro step resolutions of 200 25 600 via DIP switches 8 output current settings of 1 0 4 2A via DIP Switches Configurable control command smoothing for performance excellence Automatic idle current reduction to 50 or 90 Convenient self test ...

Страница 6: ...tion setup 5 0 μS Isolation resistance 500 MΩ 2 2 Environment Cooling Natural Cooling or Forced cooling Operating Environment Environment Avoid dust oil fog and corrosive gases Ambient Temperature 0 65 C 32 149 F Humidity 40 90 RH Operating Temperature 0 50 C 32 122 F Vibration 10 50Hz 0 15mm Storage Temperature 20 C 65 C 4 F 149 F Weight Approx 230g 8 oz 2 3 Mechanical Specifications unit mm 1inc...

Страница 7: ...e pulse step direction control mode this input signal represents a pulse which is active at the rising or falling voltage edge set by DIP switch SW13 in double pulse CW CCW control mode this input signal represents clockwise CW pulse which is active at both high voltage level and low voltage level PUL DIR Direction Connection Required 1 5 24V optically isolated differential 2 Maximum 200 KHz input...

Страница 8: ... or any P1 P2 P4 terminal block to avoid drive damage or injury while powered on 3 3 P4 Motor Connector PIN Details A Connect to motor A wire A Connect to motor A wire B Connect to motor B wire B Connect to motor B wire 3 5 Status LED Lights There are two LED lights for EM542S The GREEN one is the power indicator which should be always on in normal circumstance The RED one is a drive status indica...

Страница 9: ... sourcing Figure 5 Sinking output Figure 6 Sourcing output 5 Stepper Motor Connections EM542S can drive 2 phase and 4 phase bipolar hybrid stepper motors with 4 6 or 8 wires Although setting the output current to 1 4 times of motor phase current will get maximum torque from the motor at the same time motor heating will be also maximized So just configure the drive output current to a value which w...

Страница 10: ...tors under series connection has the most inductance the performance will start to degrade when the motor runs at higher speed For this connection it is suggested to set an EM542S s output RMA current to no more than 70 of the stepper motor s phase current to prevent overheating See the next figure for how to connect an 8 lead stepper motor for series connection Figure 10 8 lead motor series conne...

Страница 11: ...w leadshine com ProductSubType aspx subtype regulated switching power supplies In the case when only general purpose switching power supplies are available choose one with OVERSIZED current output rating for example using a 4A power supply for 3A stepper motor to avoid current clamp On the other hand if unregulated supply is used one may use a power supply of lower current rating than that of moto...

Страница 12: ...coils will significantly change resulting inductance and resistance it is therefore important to set drive output current depending on motor phase current motor leads and connection methods Phase current rating supplied by motor manufacturer is important in selecting drive current however the selection also depends on leads and connections The first three bits SW1 2 3 of the DIP switch are used to...

Страница 13: ...OFF 100 20000 ON OFF OFF OFF 125 25000 OFF OFF OFF OFF 7 4 Filter Time Configuration SW9 10 EM542S has an advanced feature called control command smoothing to eliminate noise input pulse from the pulse generator controller PLC etc and therefore improve motion smoothness and high speed torque performance in many circumstances This is achieved through adding filtering time which is configured SW 9 1...

Страница 14: ...s position to OFF 7 9 Shaft Lock Configuration SW15 Use DIP switch SW15 to set shaft lock mode when EM542 is disabled read ENA and ENA explanation of control connector for how to disable EM542S Set it to OFF position default for no motor shaft lock free spin when drive disabled Set it to ON position for motor shaft lock 7 10 Self Test Configuration SW16 For test and system diagnosis purpose EM42 i...

Страница 15: ...al connection 10 Sequence Chart of Control Signals In order to avoid some fault operations and deviations PUL DIR and ENA should abide by some rules shown as following diagram Figure 13 Sequence chart of control signals Remark a t1 ENA must be ahead of DIR by at least 5 s Usually ENA and ENA are NC not connected See Connector P1 Configurations for more information b t2 DIR must be ahead of PUL eff...

Страница 16: ...connection is connected the impedance mode between ALM and ALM will be changed See Fault Output Configuration section for detail Priority Time s of Blink Sequence wave of red LED Description 1st 1 Over current protection activated when peak current exceeds the limit 2nd 2 Over voltage protection activated when drive working voltage is greater than 60VDC Figure 14 Error Protections When above prote...

Страница 17: ...ems can be traced to electrical noise controller software errors or mistake in wiring Problem Symptoms and Possible Causes Symptoms Possible Problems Motor is not rotating No power Pulse revolution setting is wrong DIP switch current setting is wrong Fault condition exists The drive is disabled Motor rotates in the wrong direction Motor phases may be connected in reverse The drive in fault DIP swi...

Страница 18: ...tion or misuse or operation beyond the electrical specifications of the product and or operation beyond environmental specifications for the product Obtaining Warranty Service To obtain warranty service please contact your seller to obtain a returned material authorization number RMA before returning product for service Shipping Failed Products If your product fail during the warranty period pleas...

Страница 19: ...leadshine com Tel 86 755 2643 4369 All Regions 86 755 2641 7617 North South America 86 755 2641 7674 Asia Australia Africa 86 755 2640 9254 Europe Fax 86 755 2640 2718 Email sales leadshine com tech leadshine com Leadshine America Inc Address 26050 Towne Centre Dr Foothill Ranch CA 92610 USA Tel 1 949 608 7270 Fax 1 949 608 7298 Web http www leadshineusa com Email sales leadshineusa com Sales supp...

Отзывы: