Installation instructions
Installation of Accessories
Page 14 of 25
Connecting the CDR Power Distributor Relay
The LPS has a jumpstart function to start the vehicle when the starter battery is
discharged. In an emergency, the CDR power distributor relay ensures
controlled and current-limited charge compensation between the LPS and the
empty starter battery.
From hardware version 12.20/15.20/25.20, the jumpstart function
is also possible without CDR.
To connect the CDR power distributor relay, perform the following steps:
You need a CDR 200/40.
You need two cables (16 mm
2
).
1.
Disconnect the starter battery from the on-board power supply.
Warning: Disconnect the negative lead first.
2.
Secure one cable (16 mm
2
) of the device near the vehicle battery with a
suitable fuse (80 A).
3.
Using the fused line, connect the positive terminal of the vehicle battery
to a screw terminal of the CDR.
4.
Use a cable to connect the same screw terminal of the CDR with the
positive contact of the grey Anderson plug.
5.
Use a cable to connect the negative terminal of the vehicle battery to the
negative contact of the grey Anderson plug.