The connection is made using 7 female connectors euroblock type with 3 contacts and
pitch 3.81 mm (supplied with the unit). The wire size range for each pole of this connector is:
0.14
1.5 mm2 (30
14 AWG).
Marking
Description
Type
Signal
s
Activation
GPIO X
Port General Purpose I / O
configurable
Input/
Output
┴ X
Output0-5V DC
Input 0-5V DC
Table 18: GPIO ports
(b) PORT FOR ADVANCED INTEGRATION WITH THE CIE
The equipment has a supervised serial communications port, RS-485,
for connection to the central fire detection system / Control and Indicating
Equipment (CIE). To select a compatible system that will connect the
equipment you should use the con figuration software.
The connection is via a female connector euroblock type of 3 contacts
and pitch 3.81 mm (supplied with the unit). The wire size range for each pole
of this connector is: 0.14
1.5 mm2 (30
14 AWG).
Marking Description
Type
Signals Activation
485-AB
Port serial connection for
integration RS485 Terminal A and
B
Port
AB
standard RS-485/9600/8/N/1
see configuration application
485
┴
Chassis or wire mesh
NA
NA
NA
Table 19: CIE Advanced Port Integration through RS-485
18
www.lda-audiotech.com
Picture 29:
Bus RS-485
for CIE
User's Manual: EN 54-16 PA/VA System LDA NEO
Picture 28: GPIO ports
Содержание NEO 8060
Страница 1: ...User s Manual EN 54 16 certified PA VA system LDA NEO...
Страница 56: ...Ver 1 1 05 2017...