background image

Regulation Instructions

See Figure 2 on the opposite page for regulating screw 

location, door control diagram & spring power adjustment

2a  Spring Power adjustment

DO NOT ALLOW THE DOOR TO SLAM INTO THE FRAME. The 

spring power should be adjusted 

only

 if more power is needed to 

close the door. Turning the spring adjustment 

B\cx

” Allen Wrench 

clockwise will increase the spring power. Maximum adjustment is 

six (6) turns.

2b  Regulation

A “normal” closing time from a 90° position is five (5) to seven (7) 

seconds, equally divided between the 

MaiN

 and 

LaTCH SPEED

If adjustments are needed, use 

C\cx

” Allen Wrench. To adjust the 

MaiN SPEED

, turn the regulating screw clockwise to slow the 

door speed, or counterclockwise to increase the door speed. 

LaTCH SPEED

 is adjusted the same way. When adjusting the 

BaCKCHECK

, turn the regulating screw clockwise to increase 

the amount of force, or counterclockwise to reduce the amount of 

force. 

DO NOT USE THE aBRUPT BaCKCHECK SETTiNg OR 

EXPECT THE CLOSER TO aCT aS a STOP!

CaUTiON

Improper installation or regulation may result in personal 

injury or property damage. Follow all instructions carefully. 

For questions, call LCN at  

877-671-7011

Electrical Checkout

after completion of installation & wiring, and with the unit 

properly powered, perform the following tests:

3a  Hold Open

With power on, open the door any position and release. The door 

should remain in the hold-open position within 10°. For a bypass 

model to hold open, the door must be opened beyond the degree of 

the door swing indicated on the label.

3b  Door

If the door does not remain in the hold open position, push the on/

off switch. Open the door again. If the shaft end of the arm still does 

not hold open, verify the proper voltage input at the solenoid leads.

3c  Power Release

Turn the power off. The shaft end of the arm should rotate and pick 

up the rest of the arm, closing the door completely. Push the on/off 

switch again to restore the power.

3d  Put on Closer Cover

After the electrical checkout is complete, fit the closer cover onto 

the closer and insert cover screws in proper locations. Hold the 

cover firmly against the mounting plate while tightening the cover 

screws securely.

3e  Rechecking the System

The system should be checked at regular intervals. It is 

recommended that steps 3a-3c be repeated every 90 days.

Electrical Data for Door Holder Solenoid

24V AC-DC N10% - 15% @ 0.075 Amp. Max.

 

120V AC-DC N10% - 15% @ 0.030 Amp. Max.

24 V Hold Open Force Adjustment

If the door is hard to pull out of the hold open position, adjust as 

shown.

iMPORTaNT

The closer leaves the factory set at a maximum holding force. 

The holding force may be decreased and increased again, but 

it cannot be increased beyond the original setting.

Turn

counterclockwise

to decrease

the holding force

+