Replacing a Thermostat Cartridge

The thermostat replacement procedure is as follows:
1.   Shut off the hot water supply and cold water supply to 

the mixing valve.

2.   Remove the four cover screws (#9) and remove the 

front cover (#26) of the valve.

3.   Remove thermostat (#11) from the valve body.  

No special tools are necessary. 

4.   Insert a dowel rod, pencil (eraser-end), or narrow pen 

into the open end of the thermostat.  Push on the dowel 

rod with your hand.  If the thermostat feels spongy 

or springy, the thermostat has lost its charge.  If the 

thermostat feels solid or hard, the thermostat is good 

and operable.

5.   Be sure that the stainless steel piston (#15) moves 

freely up and down within the liner (#21).  Lime or 

calcium buildup should be cleaned with vinegar, green 

scotch pad, or fine emery cloth.

Setting the Mixing Valve

Prior to adjusting the temperature on the emergency mixing 

valve be aware that prior to shipping this valve was tested 

and set at the factory. Please make sure that isolation 

valves and check valves are installed and that incoming 

hot and cold pressures are equal before any adjustment 

is made. If these parameters are not present, DO NOT 

proceed to “Setting the Mixing Valve” until these parameters 

are met. IT IS ADVISED TO CALL THE FACTORY PRIOR 

TO DOING ANY TEMPERATURE ADJUSTMENTS ON ANY 

LAWLER EMERGENCY THERMOSTATIC MIXING VALVE.

This mixing valve has been set at the factory to deliver 

85°F outlet flow. Should the valve require adjustment, or an 

application require a different set temperature, proceed as 

follows:
1.   Contact the proper medical and safety authorities to 

determine correct water temperature for the specific 

application.

2.   Use a spanner wrench to remove the tamper-resistant 

cap screw.

3.   Create a draw on the mixing valve by opening a 

downstream eye wash fixture.

4.   Insert a 5/32” allen key into the cap opening of the valve  

(V1) and seat in the adjustment screw (not shown). Set 

the outlet temperature by turning the adjustment screw 

clockwise to reduce temperature, counterclockwise 

to increase temperature. Use thermometer (T1) to 

measure the outlet temperature.

5.   Replace cap screw.

Repair Kits and Assemblies

  Item  Description 

Contains 

Part No.

  A 

Repair Kit 

11-12-15-18-21+B  79854-00

  B 

O-Ring & Gasket Kit 

10-14-17-22-27 

79961-00

  C  Cover Assy. 

4-5-10-26 

78271-00

  D  Piston & Liner Assembly  14-15-21-18-17 

72904-60

  E 

Thermostat Assy. 

10-11-27 

78490-00

Parts Break Down

9

26

4

10

5

12

15

25

27

22

14

21

18

11

17

Содержание 911E

Страница 1: ...d these instructions carefully before installing and follow directions as outlined Handle the mixing valve with care Model 911 E F Thermostatic Mixing Valve Emergency Eye Fashwash This installation maintenance manual covers all configurations of the Model 911E F Maximum Inlet Pressure 125 PSI Recommended Supply Pressure 65 PSI Recommended Inlet Temperature 120 F When supplying 140 F or greater add...

Страница 2: ...r is not correct readjust the mixing valve according to the section Setting the Mixing Valve 2 Observe the flow from the emergency fixtures to ensure an adequate flow of water In addition to testing for proper temperature the cold water by pass and hot water shut down features of the mixing valve should be tested weekly The test procedure is as follows 1 Test valve temperature as described in Step...

Страница 3: ...ameters are not present DO NOT proceed to Setting the Mixing Valve until these parameters are met IT IS ADVISED TO CALL THE FACTORY PRIOR TO DOING ANY TEMPERATURE ADJUSTMENTS ON ANY LAWLER EMERGENCY THERMOSTATIC MIXING VALVE This mixing valve has been set at the factory to deliver 85 F outlet flow Should the valve require adjustment or an application require a different set temperature proceed as ...

Страница 4: ...e The mixing valve must be installed with inlet check valves and the shower or the Eyewash Facewash fixture should be installed 4 to 10 feet from the mixing valve Hot and cold water inlet pressures must be equal Provisions shall be made to thermally isolate the valve WARNING This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive har...

Страница 5: ...dvisor should be consulted for the optimum temperature for each application Date T1 July Aug Sept Oct Nov Dec Jan Feb March April May June July Aug Sept Oct Nov Dec Jan Feb March April May June July Aug Sept Oct Nov Dec Date T1 Jan Feb March April May June July Aug Sept Oct Nov Dec Jan Feb March April May June July Aug Sept Oct Nov Dec Jan Feb March April May June YEAR YEAR YEAR YEAR YEAR YEAR Dat...

Страница 6: ......

Отзывы: