background image

GUARANTEE

We guarantee the Lawler Mixing Valve to be free from 

defects in workmanship and material, and for a pe-

riod of one year from date of purchase, will replace 

any parts found by us to be defective. We will not be 

held responsible, however, for any labor incidental 

to, or for any damages caused by defective mate-

rial. Each mixing valve is thoroughly inspected and 

tested under actual conditions at our factory.

-4-

Figure 1

Figure 2

Setting The Mixing Valve To The System

Typical Installation

Install the mixing valve below the hot water tank or 

heater.  If this is not possible, pipe in a heat trap as  

shown in Figure 1 with an approximate 2

 drop.

Connect a tempered water return line as shown in  

Figure  1.  This  allows  flow  through  both  ports  of  the 

mixing valve during periods of no draw.

If a dual temperature system is used, a separate re-

circulating loop and pump are required to return high 

temperature hot water to the water heater.  See Figure 2.

Install an aquastat at the tempered water return pump.

Install the water heater per manufacturer’s instructions.  

 

 1.  After  installations  be  sure  to  flush  the  system 

thoroughly.

 2.  Make sure the hot water supply is heated to normal 

design temperature.

 3.  Close and tag all fixtures to ensure they are not 

used during this procedure.

 4.  Turn off the recirculating pump.

 5. Create a draw on the system greater than the 

minimum flow rating of the mixing valve.  All open 

fixtures  must  be  tagged  to  ensure  they  are  not 

tampered with or used during this procedure.

 6.  Allow water to flow through the mixing valve until 

the water temperature is stable.  If necessary, 

readjust the mixing valve in accordance with the 

TEMPERATURE ADJUSTMENT section of the 

installation manual.

 7.  Once the temperature is set, start the recirculating 

pump and allow the system to reach set tempera-

ture.

 8.  Measure the water temperature at the return pump 

and adjust the aquastat to shut off the pump should 

the return water exceed the set point by 2 de- 

grees F.  Set the low limit switch to restart the 

return pump when return water drops 5 degrees 

F below the set temperature.

 9. If adjustment of the diverting valve is necessary, 

rotate the adjustment stem 1/16" of a turn.

10. Shut off all fixtures and ensure there is no draw 

on the system.  The cold inlet to the mixing valve 

should be warm.

11. Allow the system to run in this condition for at least 

30 minutes.

12. In some cases, an increase in water temperature  

may occur during a no draw period.  If this occurs, 

slowly close the balancing valve until the water 

temperature is back to the original set temperature.

Typical Installation

When used in a dual temperature  

recirculating system

Typical Installation

When used in a single temperature  

recirculating system

IMM000704

Отзывы: