NOTICE!

Thermostatic Water Controllers will not work satisfactorily if improperly installed. 

Read these instructions carefully before installing and follow directions as outlined. 

Checking Cold Water Shut-Off

Turn on full hot and cold water supply to the valve 

and let it run for one minute. Then shut off the hot 

water stop and check valve only. Cold water should 

flow through the controller momentarily then be re-

duced to a negligible amount. 
Failure to do so indicates that:

a. Plunger is sticking and requires cleaning or 

replacement. 

at the outlet temperature stamped on the label. 

Standard setting is 110°F. If the outlet temperature 

is different than that shown on the label, readjust 

valve according to “TEMPERATURE ADJUST-

MENT” procedure on page 2.

2.  If after adjusting the outlet temperature the wa- 

ter stays below the set temperature, see “CHECK-

ING  COLD WATER SHUT-OFF.” If the tem-

perature  stays above the set temperature, see 

“CHECKING HOT WATER SHUT-OFF.”

Caution:

 When maintaining and adjusting the 

mixing  valve,  all  fixtures  should  be  isolated  from 

use. Lawler Manufacturing Co., Inc. recommends 

that you work safely at all times and in a manner 

consistent with the OSHA Lock/Tagout standard,  

29 CFR 1910.147 and other applicable standards. 

WARNING: Opening of the actuator may result in 

electrical shock.

General Description

The Model 805 water temperature controller is care-

fully assembled and tested at the factory to mix hot 

and cold water to any desired temperature within 

range. The temperature of the hot water should be 

at least 20°F higher than the maximum valve setting. 

The major safety features are:
1.  Failure of cold water supply causes the hot water 

ports to reduce hot water flow.

2.  Failure of hot water supply causes the cold water 

ports to reduce cold water flow.

3.  Failure of the thermostat allows both ports to 

reduce flow of hot and cold water.

At each inlet of the controller is a union end stop and 

check valve with removable strainer. Stop and check 

valves are to prevent water from bypassing between 

hot and cold water supply lines. These valves should 

be fully open when in operation.

Maximum Inlet Conditions

Pressure: 125 psi

Temperature: 200°F

Maintenance

The controller should be checked periodically and, 

if needed, cleaned as outlined in “INSPECTING and 

CLEANING VALVE.” To test for proper setting and 

operation - proceed as follows:
1.  Turn on full hot and cold water supply to the 

valve. The mixing valve should deliver water 

www.temperedwater.com

5330 East 25

th

 Street

Indianapolis, Indiana 46218

Phone (317) 261-1212

Fax (317) 261-1208

       ASSE 1017 Approved

C

®

U P C

Certified to  

CSA B125.3

CAPACITIES – MODEL 803

 

 

 

Pressure Drop PSI

  

5  10 20 30 45 60 80

 

Valve Number

 

Capacity

 

803-GPM 

 

43  60  85  103 125 144 165

 

803-LPM

 

163  227 322 390 473 545 624

 

Valve A B

 Number  N.P.T. N.P.T.  C D  E

 803

 

1

1

/

4

  1

1

/

2

  12

3

/

4

 12

1

/

2

 10

3

/

4

DIMENSIONS:

Содержание 803 SEA Basic

Страница 1: ... electrical shock General Description The Model 805 water temperature controller is care fully assembled and tested at the factory to mix hot and cold water to any desired temperature within range The temperature of the hot water should be at least 20 F higher than the maximum valve setting The major safety features are 1 Failure of cold water supply causes the hot water ports to reduce hot water ...

Страница 2: ...r With the liner out of the valve replace liner O ring 10 Note If the piston or liner is nicked or shows signs of excessive wear it should be replaced Caution The liner and plunger cannot be dropped please handle carefully The liner must be in serted correctly Carefully examining the outside of the liner will reveal a very small difference in diameter between the upper half and the lower half On r...

Страница 3: ...at O Ring 36 Pushrod 37 Spring Retainer 38 Relief Spring 39 Acorn Nut 40 Nameplate NS 41 Liner Gasket Lower 42 S C Gasket NS Not Shown 12a Only available in Assembly 805 cut away 11 12 36 37 39 38 See Fig B 8 7 See Fig C 42 10 13 14 41 35 34 33 32 31 30 29 28 27 26 25 24 22 1 19 18 21 Figure B Repair Kits and Assemblies Item Description Contains Part No 1 Complete Repair Kit 7 10 12a 13 18 22 24 3...

Страница 4: ...ng this procedure 6 Allow water to flow through the mixing valve until the water temperature is stable If necessary readjust the mixing valve in accordance with the TEMPERATURE ADJUSTMENT section of the installation manual 7 Once the temperature is set start the recirculating pump and allow the system to reach set tempera ture 8 Measure the water temperature at the return pump and adjust the aquas...

Отзывы: