background image

GUARANTEE

We guarantee the Lawler Mixing Valve to be free from def ects in workmanship and material, and for 

a period of one year from date of purchase, will replace any parts found by us to be defective. We will 

not be held responsible, however, for any labor incidental to, or for any damages caused by defective 

material. Each mixing valve is thoroughly inspected and tested under actual conditions at our factory.

Typical Installation

Install the mixing valve below the hot water tank or heater.  

If this is not possible, pipe in a heat trap as shown in  

Figure 1 with an approximate 2’ drop.

Connect a tempered water return line as shown in  

Figure 1. This allows flow through both ports of the mixing 

valve during periods of no draw.

If a dual temperature system is used, a separate 

recirculating loop and pump are required to return high 

temperature hot water to the water heater. See Figure 2.

Install an aquastat at the tempered water return pump.

Install the water heater per manufacturer’s instructions.

Setting The Mixing Valve To The System

  1.   After installations be sure to flush the system thoroughly.
  2.   Make sure the hot water supply is heated to normal 

design temperature.

  3.   Close and tag all fixtures to ensure they are not used 

during this procedure.

  4.   Turn off the recirculating pump.

  5.   Create a draw on the system greater than the minimum 

flow rating of the mixing valve. All open fixtures must be 

tagged to ensure they are not tampered with or used 

during this procedure.

  6.   Allow water to flow through the mixing valve until the 

water temperature is stable. If necessary, readjust the 

mixing valve in accordance with the TEMPERATURE 

ADJUSTMENT section of the installation manual.

  7.   Once the temperature is set, start the recirculating pump 

and allow the system to reach set temperature.

  8.   Measure the water temperature at the return pump 

and adjust the aquastat to shut off the pump should 

the return water exceed the set point by 2 degrees 

F. Set the low limit switch to restart the return pump 

when return water drops 5 degrees F below the set 

temperature.

  9.   Set the balancing valve in the full open position.
10.   Shut off all fixtures and ensure there is no draw on the 

system. The cold inlet to the mixing valve should be 

warm.

11.   Allow the system to run in this condition for at least 30 

minutes.

12.   In some cases, an increase in water temperature may 

occur during a no draw period. If this occurs, slowly 

close the balancing valve until the water temperature is 

back to the original set temperature.

STORAGE

TANK

WATER

HEATER

HEAT TRAP

27” DROP

RECIRCULATION

PUMP

AQUASTAT

BALANCING

VALVE

CW

CW

HW

CV

CV

CV

CV

TO LOW

TEMPERATURE

FIXTURES

Water heater must 
be installed per
manufacturers O+M

STORAGE

TANK

WATER

HEATER

HEAT TRAP

27” DROP

RECIRCULATION

PUMP

AQUASTAT

BALANCING

VALVE

CV

CW

CW

HW

CV

CV

CV

CV

TO LOW

TEMPERATURE

FIXTURES

TO HIGH

TEMPERATURE

FIXTURES

RECIRCULATION

PUMP

Water heater must 
be installed per
manufacturers O+M

Figure 1

When used in a single temperature 

recirculating system

Figure 2

When used in a dual temperature 

recirculating system

Отзывы: