FAULT
CAUSE
SOLUTION
RESTART PROCEDURE
or
Pump overload
It stops the whole unit
or
Phase sequence
It stops the whole unit
Circuit breaker Q2
has tripped
Wrong phase
sequence at the main
power supply
Check if the electrical
connections are correct.
Check voltages, intensities
and variations. Check water
pressure. Check water
quality. Check if the pump is
blocked
Switch OFF the main power
switch, disconnect the chiller
from the power supply and
exchange two phases in the
main power supply
Disconnect the chiller by turning
Off the main power switch (see
point 4.1). Open the electrical
box (accessible through the right
panel of the chiller) and reset
the Q2 circuit breaker. Turn the
Main power switch back On
Once the phase sequence is
correct the chiller will work
normally automatically
Offline EBM 1
It stops the compressor
Q3 circuit breaker
tripped
Motor fan faulty
Check if the electrical
connections are correct.
Check supply voltage and
power surges
Contact authorized technical
service
Disconnect the chiller by turning
Off the main power switch (see
point 4.1). Open the electrical
box (accessible through the right
panel of the chiller) and reset
the Q3 circuit breaker. Turn the
Main power switch back On
Chilled water high
temperature
The water tank
temperature has been
more than 5ºC (9ºF)
above the
programmed setpoint
for some minutes
Check the cold water set
point is within the limits
indicated on point 3.1, the
ethylene glycol proportion is
correct and the antifreeze
protection is set accordingly.
Stop the application so that
it does not generate heat and
let the chiller without load
for some minutes. If the
problem persists
contact
authorized technical service
It's a warning only; the chiller is
still working normally
High water temperature
Safety Alarm
It stops the whole unit
The water inlet
temperature or water
tank temperature has
exceeded 45ºC
(113ºF)
Wait until the temperature
decreases or change the
water in the circuit and
restart the unit
Once all water temperatures are
below 45ºC, disconnect the
chiller by turning Off the main
power switch (see point 4.1).
Turn it back On after at least 30
seconds have passed