11.2
Cooling unit
Table 10: Cooling capacity
Unit
MC 250
MC 350
MC 600
MC 1200
Cooling capacity (at 20 °C)
kW
0.25
0.35
0.60
1.20
Cooling capacity (at 10 °C)
kW
0.20
0.28
0.50
1.05
Cooling capacity (at 0 °C)
kW
0.15
0.22
0.36
0.75
Cooling capacity (at -10 °C)
kW
0.09
0.16
0.15
0.40
The cooling output is measured when the heat transfer liquid rea-
ches a certain temperature. These temperature values are specified
in brackets. The ambient temperature for the measurement is 20 °C
and ethanol was used as a heat transfer liquid. To measure water-
cooled devices, the cooling water temperature is 15 °C and the
cooling water differential pressure is 3 bar.
11.3
Refrigerant and filling charge
The device contains fluorinated greenhouse gases.
Table 11: Devices with 230 V; 50 Hz
Unit
MC 250
MC 350
MC 600
MC 1200
Refrigerant
---
R-134a
R-134a
R-134a
R-134a
Maximum filling weight
kg
0.085
0.095
0.295
0.575
GWP
(100a)
*
---
1430
1430
1430
1430
CO
2
equivalent
t
0.1
0.1
0.4
0.8
Table 12: Devices with 220 V; 60 Hz
Unit
MC 250
MC 350
MC 600
MC 1200
Refrigerant
---
R-134a
R-134a
R-134a
R-134a
Maximum filling weight
kg
0.08
0.097
0.285
0.63
GWP
(100a)
*
---
1430
1430
1430
1430
CO
2
equivalent
t
0.1
0.1
0.4
0.9
Table 13: Devices with 115 V; 60 Hz
Unit
MC 250
MC 350
MC 600
MC 1200
Refrigerant
---
R-134a
R-134a
R-134a
R-134a
Maximum filling weight
kg
0.08
0.095
0.225
0.585
V07
Microcool