Integral XT
YAWE0028 / 24/06/2016
Maintenance
135
Three-phase alternating
current units
Order no.
Circuit boards
UL 555-9 (power
supply)
UL 571 (heating)
UL 563 (distributor 2)
XT 1850 W
LWP 532
400 V; 3/PE~50 Hz
F3, F4
à
see table (
þ
2x UL 555
F1 to F6
à
F10A0 (quick
blow) EES 067
---
XT 1850 W
LWP 632
440-480 V; 3/PE~60 Hz
F3, F4
à
see table (
þ
2x UL 555
---
F1 to F6
à
FF12A5
(extra quick blow)
EES 015
XT 1850 W
LWP 732
400 V; 3/PE~50 Hz +
440-480 V; 3/PE~60 Hz
F3, F4
à
see table (
þ
---
F1 to F6
à
FF12A5
(extra quick blow)
EES 015
XT 1850 WS
LWP 533
400 V; 3/PE~50 Hz
---
F1 to F6
à
FF 16A
(extra quick blow)
EES 071
+
For the PCB UL 555 and the fuses F3 and F4, consider the following:
−
Only use UL fuses (listed according to UL 248-14)!
Table fuses for three-phase alternating current units