CHAPTER 4
COMMUNICATION PROTOCOLS
4-12
DC-24 and DC-25 operation manual
Function 10h mode ASCII
Sending temperature and humidity using the function 10h.
In the frame, the following codes must be codified.
Unit = 01h
Function = 10h
Start address = 00h 00h
Identifier
Protocol
Num. bytes
Unit
Function
Start address
00h 37h
00h 00h
00h 11h
01h
10h
00h 00h
Num. Registers
Num. Bytes
Data
Data
00h 05h
0Ah
56h 54h
31h 39h 2Eh 34h 20h 35h 37h
In this example, in the data field the values 19,4°C 57% must be sent.
Response from the display:
The response from the display is the same frame received from the identifier until the number of
registers.
Identifier
Protocol
Num.
bytes
Unit
Function
Start
address
Num.
Registers
00h 37h
00h 00h
00h 11h
01h
10h
00h 00h
00h 05h
Function 10h mode Word
Sending temperature and humidity can be sent using the function 10h.
In the frame, the following codes must be codified.
Unit = 01h
Function = 10h
Start address = Register 40003 (Address 02h)
Identifier
Protocol
Num. Bytes
Unit
Function
Start address
00h 37h
00h 00h
00h 0Bh
01h
10h
00h 02h
Number of registers
Number of bytes
Data
00h 02h
04h
00h F3h 00h 39h
In this example, in the data field the values 19,4°C 57% must be sent.
Response from the display:
The response from the display is the same frame received from the identifier until the number of
registers.
Identifier
Protocol
Number of
bytes
Unit
Function
Start
address
Number
registers
00h 37h
00h 00h
00h 0Bh
01h
10h
00h 00h
00h 04h