BUCK & BOOST TRANSFORMERS 

Ventilation 

Transformers are required to maintain free air flow around the unit for cooling purposes. The location should 
maintain an average ambient temperature of 86°F (30°C) and should not exceed 104°F (40°C) at any time. 
Proper ventilation is essential for transformers to meet their kVA capability. General purpose transformers 
should be located at least 2 inches for 10kVA and 4 inches for units over 10kVA from the surface to maintain 
adequate air circulation. 

Accessibility 

Due to NEC standards, it is required for transformers to be accessible for inspection and located accordingly. 
Exposed passage ways where people could be exposed to live parts during inspection should be avoided. 

Sound Levels 

By nature, transformers emit sound frequencies due to their electrically energized components. Care should be 
exercised when selecting a location to avoid sensitive areas such as in schools, hospitals, and office facilities. 
The sound levels produced by these transformers are required to meet NEMA standards. The sound level can 
vary from 40 to 60 DB. Acoustically absorbing materials could be considered for surrounding walls and 
ceilings. 

Wire Connections 

1. 

Loosen the cover screw on the front to open the wiring compartment. 

2. 

Ensure terminals are clean. Use the included lugs and bolts for terminal wiring where applicable. Use 
wire nuts or similar for all other electrical connections. 

3. 

Make the required electrical connections per the wire diagram on page 4-6. This includes input and 
output connections, as well as ground(s). 

4. 

If any unused wire leads remain, insulate with wire nuts and electrical tape. 

5. 

Inspect all connections and close the wiring compartment. Secure the cover screw. 

Proper cable size is selected based on the line current rating of the transformers primary and secondary sides. 
Pre-punched knockouts are provided to help facilitate cable entry. 

Ground 

Grounding should be done in accordance with national electrical code standards. Securely grounding the 
transformer should be done as a safety precaution. 

For safe and proper operation of the transformer, we recommend the following items be checked for 
completeness: 

  Insulation resistance: enclosure to primary, enclosure to secondary and primary to secondary should be 

greater than 10k ohms. 

  Output voltage: measure and verify that the transformer outputs the correct voltage in accordance with 

nameplate specifications. Voltage may vary depending on actual power available at your facility. 

  Phase connections: refer to the nameplate diagram to ensure correct phase connections. 

  When windings are connected in parallel (in the case of dual voltage primaries), the primary taps for all 

coils must be connected to the identical percentage tap positions to avoid the shorting of turns. For tap 
positions, refer to the transformer nameplate. 

Содержание MT-BBT-480Y-380Y.220-3P-781A

Страница 1: ...ansformer Type Buck Boost Step Down Autotransformer NRTL Listed for United States Phase Three Phase CSA Certified for Canada Frequency 50 60 Hz NEMA 3R Indoor Outdoor Enclosure Input Voltage 480 V Wye...

Страница 2: ...ulated in silica sand and resin and cased in a NEMA 3R steel enclosure NEMA 4 NEMA 4X and NEMA 12 enclosures are available upon request Benefits The MT BBT 480Y 380Y 220 3P 781A buck boost step down t...

Страница 3: ...Boost Transformers Standard Industrial Transformers Note on Phases This buck boost transformer is a three phase step up transformer For single phase transformers click on the following link Single Ph...

Страница 4: ...ted These details with all relevant information should also be forwarded to Larson Electronics Use appropriate measures and experienced personnel for transporting the transformer relative to its size...

Страница 5: ...erminals are clean Use the included lugs and bolts for terminal wiring where applicable Use wire nuts or similar for all other electrical connections 3 Make the required electrical connections per the...

Страница 6: ...ent temperatures required for transformer operation Short time overload as it relates to time and temperature and the corresponding loss of life of the transformer Overload that results in the reducti...

Страница 7: ...ne 800 369 6671 Fax 903 498 3364 www larsonelectronics com 4 of 7 DIAGRAM L BUCK BOOST TRANSFORMERS Connection Diagram Refer to the diagrams below for connecting the transformer Choose the type that r...

Страница 8: ...Larson Electronics LLC Phone 800 369 6671 Fax 903 498 3364 www larsonelectronics com 5 of 7 DIAGRAM L BUCK BOOST TRANSFORMERS TYPE A TYPE B...

Страница 9: ...d X1 together for each transformer 3 Connect High Voltage PHASE A to X4 X2 on transformer 1 4 Connect High Voltage PHASE B to X4 X2 on transformer 2 5 Connect High Voltage PHASE C to X4 X2 on transfor...

Страница 10: ...Larson Electronics LLC Phone 800 369 6671 Fax 903 498 3364 www larsonelectronics com 7 of 7 DIAGRAM L BUCK BOOST TRANSFORMERS...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...Frequently Asked Questions FAQ...

Отзывы: