INSTALLATION
CIRC
U
IT
B
REA
K
ER INSTALLATION
Make sure that the equipment is suitable for the installation by comparing nameplate ratings with system requirements.
Inspect the equipment for completeness and check for any damage.
WARNING:
MAKE SURE POWER IS TURNED
OFF
BEFORE STARTING THE
INSTALLATION OR PERFORMING ANY MAINTENANCE.
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
1. Before mounting the circuit breaker in an electrical system, make sure there is no voltage present
where work is to be performed.
2. Mount no closer to enclosure metal or live parts than is indicated in drawing.
3. All enclosure closing hardware must be installed.
FAILURE TO FOLLOW THESE INSTRUCTONS WILL RESULT IN DEATH OR SEVERE INJURY.
<Table.1>
Size of Enclosure /
Tamaño del cierre /
Taille du boîtier
●
Dimensions / Dimensiones / Dimensions: inch / pulg / inch(mm)
Metal or Live Electrical Parts / Partes eléctricos metales o
vivos /Métal ou pièces électriques sous tension
<Fig. 1>
Clearances for Circuit Breaker / Espacio libre para el interruptor / Dégagements pour disjoncteur
<Fig. 2>
Circuit Breaker Mounting
Bolt Drilling Plan /
Plan de perforación de
tornillo de montaje del
interruptor/ Plan de forage
des Vis de montage du
Disjoncteur
<Fig. 3>
Circuit Breaker
Escutcheon
Dimensions /
Dimensiones del escudo
del interruptor /
Dimensions d’écusson
du Disjoncteur
W
H
D
W
1.1.89
89 ((448)8)
1.
1.06
06
(2
(27)
7)
#6-32
#6-32 UNC
UNC
T
ap (2
ap (2 Holes)
Holes)
4.4.33
33
[1
110
]0]
4.4.33
33
[1
110]0]
0.
0.98
98
[2
[25]
5]
0.
0.49
49
[12
[12.5]
.5]
[2
[2P]
P]
[3
[3P]
P]
#6-32
#6-32 UNC
UNC
T
ap (2
ap (2 Holes)
Holes)
80% and 100% RATED inch / pulg / po (mm)
W
H
D
a
b
c
Circuit
Breaker
Type
UTE100
2P, 3P
17.3
(439.4)
8.27
(210)
3.94
(100)
2.58
(65.4)
6.03
(153.1)
3.29
(83.5)
Dimensions for electrical and mechanical clearance to metal or live electrical parts.
(See Fig. 1) To mount the circuit breaker perform the following steps:
1. For individual surface mounting, drill and tap mounting bolts holes according to the drilling plan shown in Fig. 2.
For dead- front cover applications, cut out cover to correct escutcheon dimensions refer to Fig. 3 .
2. If circuit breaker includes factory-or field-installed internal accessories, make sure that accessory wiring can be reached when the
circuit breaker is mounted.
3. Position circuit breaker on mounting surface.
4. Install circuit breaker mounting screws and washers. Tighten hardware securely, but do not exceed 13.3 pound-inches (1.5N.m.)
MPD-XX-CB-SF-489