EXP-TSTAT-125.250-60.250F-0.25-V1-15L

4.

Remove white shaft coupler for safe-keeping while making
wiring connections (see Figure 6).

5.

Connect wires according to wiring diagrams (Figures 7 thru 11).

Note:

Electrical connections should be made with generous

loops of wire — approximately 6” per lead.

6.

Replace white shaft coupler.

7.

WARNING:

It is possible to replace enclosure

cover with adjustment knob 180 rotational
degrees out of alignment resulting in large cali-
bration errors. To avoid this, carefully follow
these procedures.

A.

Be sure that thermostat shaft is fully counter-clockwise (see
Figure 12). With thermostat knob held in the indicated OFF
position, carefully replace enclosure cover while feeling for
proper engagement of
shaft coupling.

B.

With cover screws replaced
and moderately fastened,
check for full rotation of
dial knob. 

Note:

Mild shaft

resistance should be
encountered. If satisfied,
that proper engagement of
shaft coupler is accom-
plished; finish tightening
cover screws.

8. Note:

If load amperage or

voltage rating exceeds switch
rating, a contactor must be
used. Contactor and wiring to
be supplied by customer (see

WIRING

Dial
Stop
Post

Stop

Tab

Figure 12

Figure 6

1

2

3

4

1

2

3

4

Pilot
Light

Load

Line

Single Phase

Pilot Light

Load

Line

Single Phase

1

2

3

4

Pilot Light

Line

Load

Load

Two Circuit

1

2

3

4

1

2

3

4

Pilot
Light

Line

Three Phase
when Load
Does Not
Exceed
Rating of
Thermostat

}

Three Phase
and Single
Phase when
Load Exceeds
Rating of 
Thermostat

Control
Voltage

Line

Load

Pilot
Light

Contactor

Figure 7

Figure 8

Figure 9

Figure 10

Figure 11