When the power is turned ON, the red and green LEDs flash for few seconds.
•
During a detection the red LED lights illuminates.
•
During configuration, the red LED flashes a number of times corresponding to the parameter being changed (see
next table). The green LED flashes a number corresponding to its setting.
8
EXP-MS-30W-N4X | Larson Electronics, LLC
Page
3
of
4
POSSIBLE SETTINGS BY REMOTE CONTROL
1-6
-75°
-60°
-45°
Choose the right detection filter for your application with the remote control
Value recommendations according to angle and height:
Detection of all targets
(pedestrians and parallel traffic are detected)
1 = no specific filter
2 = filter against disturbances
(recommended in case of vibrations, rain etc.)
Detection only of vehicles moving*
(pedestrians and parallel traffic are not de disturbances are filtered)
* The vehicle detection filter increases the response time of the sensor.
Always check if the chosen
value is optimal for the appli-
cation.
The object size and nature
can influence the detection.
23 ft - 11.5 ft 8 ft
3
4
5
DETECTION FILTER
(REJECTION MODE)
3
4
4
LED SIGNALS
POSSIBLE SETTINGS BY PUSH BUTTONS
(7)
(0)
(1)
(2)
(1)
TO START OR END AN ADJUSTMENT SESSION
, press and hold either push button until the LED flashes or stops
flashing.
1
FIELD SIZE
Parameter number
2
HOLD-OPEN TIME
3
OUTPUT CONFIGURATION
4
DETECTION MODE
5
DETECTION FILTER
Value (factory values)
TO SCROLL THROUGH THE
PARAMETERS, press
the right push button.
TO CHANGE THE VALUE
OF THE CHOSEN
PARAMETER, press the left
push button.
TO RESET TO FACTORY VALUES
, press and hold both push buttons until both LEDs flash.
FIELD SIZE
OUTPUT
CONFIGURATION
DETECTION MODE
FACTORY VALUES
RESETTING TO FACTORY VALUES:
DETECTION FILTER
RELAY HOLD TIME
XXS
XS
S
>
>
>
>
L
XL
XXL
0.5 s
1 s
2 s
3 s
4 s
5 s
6 s
7 s
8 s
9 s
3
4
5
6
1
2
P
A
A = active output
(relay active when detection)
P = passive output
(relay active when no detection)
uni
AWAY
bi = two-way detection
uni = one-way detection towards sensor
uni AWAY = one-way detection away from sensor
bi
uni
CHECKING A VALUE
Red
Red
X
Green
Off
X = number of flashes = value of parameter