Calibration

The unit requires no calibration. An internal precision resistor continually self calibrates the unit. Calibration may be verified 

by removing the sensor leads and testing the unit against a precision RTD simulator or a precision decade box. If the unit 
is found to be out of calibration it must be returned to the factory for service.

ELECTRICAL CONNECTIONS

Connect wire leads in accordance with local electrical codes. For units supplied with both internal ground and 

external bonding terminals, the ground screw inside the housing must be used to ground the control. The external 

bonding screw is for supplementary bonding when allowed or required by local code. When external bonding 

conductor is required, conductor must be wrapped a minimum of 180° about the external bonding screw. See below.

FRONT VIEW DETAIL

BOTTOM VIEW DETAIL

CLAMP 

PLATES

LOCKWASHER

SCREW

CONDUCTOR

EU-Type Certificate, IECEx Installation Instructions:

Cable Connection

The cable entry device shall be certified in type of explosion protection flameproof enclosure “db”, suitable for conditions 

of use and correctly installed. For ta ≥ 70°C cable and cable gland rated ≥ 75°C (MIN.) shall be used.

Conduit Connection

An Ex db certified sealing device such as a conduit seal with setting compound shall be provided immediately to the 

electrical entrance of the transmitter housing. For 

ta ≥ 70°C wiring and setting compound, in the conduit seal, rated ≥ 75°C shall be used.

Unused  entries  shall  be  sealed  with  an  Ex  certified blanking  device  rated  for  the appropriate  zone,  equipment  group 

and  temperature  classification and  shall  be installed per manufacturer instructions.

Note:

 For ATEX/IECEx units only: When employed in a Zone 1, EPL Gb (db) application, the temperature class is 

determined by the maximum ambient and or process temperature. Units are intended to be used in ambient of -20°C≤ 

Tamb  ≤70°C.  Units may be used in process temperatures up to 120°C providing the enclosure temperature  do  not 

exceed  70°C.  The  standard  Temperature  Class  is  T6  Process  Temp  ≤80°C.  Remaining  temperature  classes  are, 

Temperature Class of T5 Process Temp ≤95°C and Temperature Class T4 Process Temp ≤ 120°C. Refer to Certificate 

No: Element IECEx EMT17.0007X for conditions of safe use for IECEx compliant units. All wiring, conduit and enclosures 

must meet applicable codes for hazardous areas. Conduits and enclosures must be properly sealed. For outdoor or other 

locations  where  temperatures  vary  widely,  precautions  should  be  taken  to  prevent  condensation  inside  enclosure. 

Electrical components must be kept dry at all times.

When employed in a Zone 20, EPL Da (ta) application, the equipment is to be used with a power source rated for a 

prospective short circuit current of 10 kA. If the power source is rated for a prospective short circuit current of less than 

10 kA, the end user or installer must mark the equipment with the prospective short circuit current rating of the power 

supply it is used in conjunction with.

Содержание EPSW-TS-RTD-6P-R1

Страница 1: ...ROUNDING CONDUCTOR TO AVOID EXPLOSION MAKE SURE THE SUPPLY VOLTAGE IS WITHIN THE VOLTAGE RATING ENSURE THE MARKED T RATING IS LESS THAN THE IGNITION TEMPERATURE OF THE HAZARDOUS ATMOSPHERE DO NOT OPERATE IN AMBIENT TEMPERATURES ABOVE THOSE INDICATED ON THE PRODUCT NAMEPLATE DO NOT OPERATE IF THE LENS CORD SEALS HOUSING RECEPTACLES ETC IS CRACKED OR DAMAGED IF SO DISCONTINUE USE AND CONTACT MANUFAC...

Страница 2: ... of wire size and receiver resistance Wiring should not contribute more than 10 of the receiver resistance to total loop resistance For extremely long runs over 1000 feet choose receivers with lower resistance to minimize the size and cost of connecting leads Current 4 20 mA Output Operation An external power supply is required See Figure A for diagram of the connection of the power supply transmi...

Страница 3: ...3 Wire instrument as previously discussed A current meter may be wired in series with the unit to verify the correct current output but this is not necessary for calibration Apply power to the unit 4 If a precision RTD simulator is used make sure it is set to simulate a 1000 OHM DIN 0 00385 RTD Then set it to the desired minimum temperature If a decade box is used refer to the table in Appendix A ...

Страница 4: ...e of the transmitter housing For ta 70 C wiring and setting compound in the conduit seal rated 75 C shall be used Unused entries shall be sealed with an Ex certified blanking device rated for the appropriate zone equipment group and temperature classification and shall be installed per manufacturer instructions Note For ATEX IECEx units only When employed in a Zone 1 EPL Gb db application the temp...

Страница 5: ... the product WARNING To prevent ignition of hazardous atmospheres disconnect the device from the supply circuit before opening Keep assembly tightly closed when in use CAUTION USE AND CARE Unauthorized modification may impair the function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out parts before using the device Store it in a secure p...