EPS-PB10-MS-AT-V4

 

 

 
 

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

 

 

This device complies with requirements of Underwriters Laboratories, Inc. for use in hazardous 
locations, as listed on the device when used with suitable enclosures. 

 

WARNING:

 To avoid risk of explosion, all flat machined surfaces must be kept clean and free from 

scratches, dents, debris, paint, and corrosion. The flat machined surfaces are explosion proof joints, and 
must be clean and undamaged on both the enclosure and cover. 

 

INSTALLATION

 

 

1. 

The surfaces of the flat ground joint are precision machined to insure an explosion proof joint 
and must be protected from scratches or damage during installation. 

2. 

When switch is mounted in the enclosure, it must be mounted to agree with cover indication of 
operation. That is, when the cover indicates ON, the switch must be in the ON condition. 

3. 

Before the cover is installed, the flat ground joint surface must be thoroughly wiped clean of any 
dirt, grit, or other foreign substances and a light thin coating of lubricant placed on the joint to 
prevent possible corrosion. 
The joint between the box and the cover has been made accurately to .001

5” to prevent the 

passage of this accuracy is destroyed. 

4. 

ALL cover screws must be installed with at least five full threads engaged and must be securely 
tightened. All cover openings must be closed with a suitable cover. 

5. 

Gaskets must not be added to these devices. Only gaskets designed for and permanently 
installed in these devices may be used. 

6. 

In accordance with the hazardous location information specifying Class and Group listing marked 
on the device, sealing fittings must be added that will comply with requirements in the latest issue 
of the Canadian Electrical Code or National Electrical Code and any special requirements that are 
stated in the instruction sheet with the enclosure. 

 

MAINTENANCE

 

 

Before removing the cover from any such device for inspection or maintenance, the power supply circuit 
must be OFF. 

 

WARNING: 

To prevent risk of explosion, hammers and prying tools must not be used to remove covers 

off enclosures. Damage to the explosion proof flat machined surfaces on cover and enclosure may 
result. Handle covers carefully. Do not place them on surfaces that might damage or scratch the flat 
machined surfaces. 

 

Before replacing the cover, after it has once been removed, the flat ground joint surfaces must be 
cleaned as described in step 3 under installation. 

 

WARNING: 

To prevent risk of explosion, replace devices if the flat machined surface is damaged, 

scratched, dented, or corroded. Field rework of flat machined surfaces is not possible. 

 

TIMER

 

A solid-state, encapsulated time delay relay can be found inside the switch, which offers an 
adjustable timer range of 2-30 seconds. When the button is engaged, the circuit stays closed, 
keeping the connected motor or device running for the set duration (between 0.1-102.3 Seconds 
in 0.1s increments). The timer component features a repeating accuracy value of +/- 0.5% and a 
setting accuracy value of +/- 2%.