EPL-LED-150W-RT-DIMM
Larson Electronics, LLC
Phone: (800) 369-6671
Fax: (903) 498-3364
www.larsonelectronics.com
4
of
5
WIRING
(see attached wiring diagram)
This unit comes preconfigured in selected voltage and beam configuration. Wire light to the correct
voltage. Follow all applicable local, state, and National Electrical Code for the hazardous area.
Wire size is 18/5.
Voltage:
Check product label for correct voltage.
Use only 0-10V Dimmer appropriate for the location installed.
WARNING:
Mis-wiring Low Voltage Dimming Control could cause permanent damage to light.
DO NOT
connect dimming control to line voltage.
DO NOT
connect dimmer with power applied.
WIRE(AC)
WIRE(DC)
COLORED CABLE
AC LIVE
DC LIVE
BLACK
AC NEUTRAL DC NEUTRAL
WHITE
GROUND
GROUND
GREEN
D D
RED
DIMMING -
DIMMING -
ORANGE
WARNING:
CHECK NAMEPLATE FOR PROPER VOLTAGE.
DAMAGE FROM IMPROPER VOLTAGE WILL VOID WARRANTY.