INSTALLATION

NOTE:

  Make sure the necessary branch circuit wiring is available. An unswitched source of power is 

required. The emergency driver must be fed from the same branch circuit as the AC driver.

CAUTION: DO NOT JOIN CONVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS 

SUPPLIED TO THE EMERGENCY DRIVER.

>

Mounting Height:

 This product meets or exceeds the NFPA minimum light requirements with all loads, down to the

smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors infl uence emergency illumination levels, such as
the lamp load selected, luminare design, and environmental factors therefore end use verifi cation is necessary. For fi eld
installations, when the attached luminaire is mounted at heights greater than 7.17ft (2.2m), the level of illumination
must be measured in the end application to ensure the requirements of NFPA 101 and local codes are satisfi ed.

>

Remote Mounting:

 The emergency LED driver may be remote mounted from the luminaire. If used in conjunction with

an AC driver the allowed distance is up to half the distance the AC driver manufacturer recommends remote mounting
the AC driver from the LED load. If used without an AC driver, and remote mounting more than 5 feet from the luminaire,
please consult the factory to determine the necessary wire gauge. 

CAUTION:

 Remote mounting can result in reduced

power output.

EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

WIRING DIAGRAMS

FIG A  TWO (2) WIRE INTEGRATED TEST SWITCH

:$//6:,7&+

:+75('

9,2/(7

%52:1

+27

%/$&.

$&'5,9(5

:+,7(

:+7%/.

&20021

<(//2:

<(/%/.

%/8(

/('

/('

$&'5,9(5

$&'5,9(5

/('/2$'

:+,7(

%/$&.

5('

5('

&219(57(5
&211(&725

%52:1

9,2/(7

(PHUJHQF\

/('

'ULYHU

*5((1

FIG B  EMERGENCY ONLY

TYPICAL SCHEMATICS ONLY.  MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

9,2/(7

%52:1

+27

%/$&.

:+,7(

:+7%/.

&20021

<(//2:

<(/%/.

%/8(

/('

/('

/('/2$'

5('

5('

&219(57(5
&211(&725

%52:1

9,2/(7

(PHUJHQF\

/('

'ULYHU

&$3

&$3

*5((1

:+75('

&$3

NOTE:

  

For short-term testing of the emergency function, the battery must be charged for at least one hour. The
emergency driver must be charged for at least 24 hours before conducting a long-term test.

During normal operation AC power is applied, the charging indicator light is illuminated, indicating that the battery is 
being charged.  When power fails, the emergency LED driver automatically switches to emergency power (internal battery), 
operating the LED load for a minimum of 90 minutes. When AC power is restored, the emergency driver returns to the 
charging mode.

Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to 
ensure that it is working. The following schedule is recommended:

1.

Visually inspect the charging indicator light monthly. It should be illuminated. If the charging indicator is
flashing. 

Contact 

tech 

support.

2.

Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. The LED load
should operate at reduced illumination.

3.

Conduct a 90-minute discharge test once a year. The LED load should operate at reduced illumination for at
least 

90 

minutes.

! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !

OPERATION

MAINTENANCE