EMGBALL-LED1-LV

 

Larson Electronics, LLC

 

 Phone: 

877-348-9680

 

Fax: (903) 498-3364 

www.larsonelectronics.com 

2

 of 

4

 

1.

Do not join converter connector until installation is complete and AC Power is supplied to the emergency driver.

2.

This product is for use with an emergency LED lighting load and supplies nominal 10.0 W of power with a 

maximum voltage of 50 VDC in emergency mode for a minimum of 90 minutes.

3.

Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and 

any local regulations.

4.

To reduce the risk of electric shock, disconnect both normal and emergency power supplies and converter 

connector of the emergency driver before servicing.

5.

This emergency driver is suitable for factory installation only.

6.

This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +55ºC 

maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable

7.

for heated air outlets and wet or hazardous locations. Maximum allowable case temp is 65ºC. See Page 4 for 

Tcase measurement location.

8.

An unswitched AC power source is required (120-277 V AC, 50/60 Hz).

9.

Do not install near gas or electric heaters.

10.

Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. 

Contact the manufacturer for information on service.

11.

The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

12.

Do not use this product for other than intended use.

13.

Servicing should be performed by qualified service personnel.

14.

Equipment should be mounted in locations and at heights where it will not be subjected to tampering by 

unauthorized personnel.

15.

For Canadian application the output terminals should be in compliance with the accessibility requirement of the 

Canadian Electric Code.

16.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this 

device may not cause harmful interference, and (2) this device must accept any interference that may cause 

undesired operation.

17.

This product must be grounded. See the wiring diagrams for details.

INSTALLATION

CAUTION: DO NOT JOIN CONVERTER CONNECTOR UNTIL INSTALLATION IS 

COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY DRIVER.

NOTE:

  Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The 

emergency driver must be fed from the same branch circuit as the AC driver. 

Mounting Height:

 This product meets or exceeds the NFPA minimum light requirements with all loads, down to 

the smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors infl uence emergency illumination 

levels, such as the lamp load selected, luminare design, and environmental factors therefore end use verifi 

cation is necessary. For fi eld installations, when the attached luminaire is mounted at heights greater than 7.17ft 

(2.2m), the level of illumination must be measured in the end application to ensure the requirements of NFPA 

101 and local codes are satisfi ed.

Remote Mounting:

 The emergency LED driver may be remote mounted from the luminaire. If used in 

conjunction with an AC driver the allowed distance is up to half the distance the AC driver manufacturer 

recommends remote mounting the AC driver from the LED load. If used without an AC driver, and remote 

mounting more than 5 feet from the luminaire, please consult the factory to determine the necessary wire gauge. 

CAUTION:

 Remote mounting can result in reduced power output.

Содержание EMGBALL-LED1-LV

Страница 1: ...EMGBALL LED1 LV INSTRUCTION MANUAL ...

Страница 2: ...ISK OF FIRE OR ELECTRIC SHOCK FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY VOLTAGE IS THE SAME AS THE FIXTURE S RATED VOLTAGE TO PREVENT WIRING DAMAGE OR ABRASION DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR SHARP OBJE...

Страница 3: ...t will not be subjected to tampering by unauthorized personnel 15 For Canadian application the output terminals should be in compliance with the accessibility requirement of the Canadian Electric Code 16 This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interfere...

Страница 4: ...operate at reduced illumination 3 Conduct a 90 minute discharge test once a year The LED load should operate at reduced illumination for at least 90 minutes REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL USE AND CARE Unauthorized modification may impair the function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out pa...

Страница 5: ...RIVERS CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS FIG A TWO 2 WIRE INTEGRATED TEST SWITCH 6 7 7 5 9 2 7 52 1 27 5 9 5 7 7 20021 2 8 5 9 5 5 9 5 2 7 5 5 219 57 5 211 725 52 1 9 2 7 PHUJHQF ULYHU 5 1 FIG B EMERGENCY ONLY 9 2 7 52 1 27 7 7 20021 2 8 2 5 5 219 57 5 211 725 52 1 9 2 7 PHUJHQF ULYHU 3 3 5 1 7 5 3 NOTE For short term testing of the emergency function the battery must be charged for at...